E T C   I n s t a l l a t i o n   G u i d e

Automatic Load Control Relay

Automatic  Load  Control  Relay

Page 8 of 8

Electronic Theatre Controls, Inc.

Examples of Use

Normal Light Fixture

Emergency Light Fixture

ALCR

Dimmer Neutral (White)

Dimmer Hot Feed

Emergency Load

Emergency Hot

Emergency Neutral (Gray)

Dimmer Control with D20FB

  •  When normal power is present, normal fixture(s) dim
     and emergency fixture(s) remain off
  •  When normal power is lost or dimmer circuit
     breaker trips, emergency fixture(s) turns on

0-10V Fixture Control (ALCR-DIN only)

  •  When normal power is present and switch is
     closed, both 0-10V controlled fixture(s) dim.

  •  When normal power is present and switch is open,
     both 0-10V controlled fixture(s) turn off.

  •  When normal power is lost or fire alarm connection
     is broken, all fixture(s) turn on to full - 0-10V
     connection is opened.

Dimmed Circuit

ETC D20FB 

module in 
Sensor or 

Unison Dimmer 

Rack

Emergency Light Fixture

ALCR

Normal Neutral (White)

Normal Hot (Black)

Emergency Load

Emergency Hot

Emergency Neutral (Gray)

Backup Arrangement

  •  When normal power is present, the emergency
     load is turned off
  •  When normal power is lost, the emergency load
     turns on

 * Cap end with wire nut or other suitable method to
    prevent contact with bare wire.

Emergency Light Fixture

Normal Neutral (White)

Normal Hot (Black)

Normal Switch

(Red)

Emergency Load

Emergency Hot

Emergency Neutral (Gray)

ALCR

Normal Light Fixture

Switch Control Arrangement

  •  When normal power is present, switch controls both
     the normal and emergency light fixtures
  •  When normal power is lost, the emergency light
     fixture(s) turn on regardless of the switch state

Normal Switch

(Red)

WIRE

  

NUT

A

UTOMATED

 L

OAD

 

C

ONTROL

 R

ELAY

(ALCR-DIN)

Status 
LED

Option 
Button

Remote 
LED

Emergency Load

Normal 

Neutral (White)

Normal Hot (Black)

Emergency Neutral (White)

Emergency Hot

0-10V signal

0-10V signal

0-10V common

0-10V 

controller

0-10V Non-Emergency Fixture

0-10V Emergency Fixture

0-10V /

FLO

Remote

Loop

Emergency

Out

Neutral

In

Normal

Switch

Sense

Neutral

Summary of Contents for ALCR-DIN

Page 1: ...rol Relay ALCR is a UL 924 listed device that is powered from an emergency source and provides power to emergency lighting load s The ALCR ensures a lights on state during loss of normal power while t...

Page 2: ...DIN rail 35mm complies with DIN43880 and EN60715 Reference Installation and Termination of the ALCR DIN on page 4 Once installation of the Automatic Load Control Relay is complete reference Configurat...

Page 3: ...s to the normal lighting circuit as shown b Connect the Normal Neutral White 18 AWG lead to the normal Neutral for the lighting loads Step 6 Proceed to Initial Test on page 7 Step 7 If you are install...

Page 4: ...single pole contacts on the remote device or test switch Step 3 Continue to Remote Activation Test on page 7 Installation and Termination of the ALCR DIN The ALCR DIN is designed to attach to lighting...

Page 5: ...ch Sense and Normal Neutral screw terminals as shown Step 4 If you are connecting to 0 10 Vdc Fluorescent lighting loads connect to the provided terminals labeled 0 10V FLO Reference Examples of Use o...

Page 6: ...a user configurable delay time between regaining normal power and removing power from the emergency lighting This delay time could be used to account for loads that may require a warm up time for exam...

Page 7: ...f reconnect the Normal Power Switch wire to the terminal Step 6 Turn On the normal circuit breaker The ALCR should now behave as described in the Examples of Use on page 8 Step 7 If you are installing...

Page 8: ...gency Light Fixture ALCR Normal Neutral White Normal Hot Black Emergency Load Emergency Hot Emergency Neutral Gray Backup Arrangement When normal power is present the emergency load is turned off When...

Reviews: