E T C   I n s t a l l a t i o n   G u i d e

Automatic Load Control Relay

Automatic  Load  Control  Relay

 Page 4 of 8

Electronic Theatre Controls, Inc.

Installing a Remote Activation Input to the ALCR-PP

The ALCR-PP offers a normally closed, dry contact input to accommodate connection 
to fire alarm panels, security systems, and test switch. This input ships from the factory 
with a blue wire loop off the right side of the unit, this complete loop disables remote 
activation. Do not cut this jumper unless you are installing a remote triggering device.

The remote device that triggers the Emergency circuit “On” must provide a normally 
closed, maintained dry contact closure for fire alarms, etc. When the remote device is 
activated, the contact closure opens and the contacts force the ALCR-PP into the 
emergency “On” state.

Step 1:

Cut the blue wire loop in the middle of the wire lead. Doing this provides two leads 
which are the connection point for both the contact input and contact output 
connections to a remote triggering device.

Step 2:

Connect the two leads to the normally closed single pole contacts on the remote 
device or test switch.

Step 3:

Continue to 

"Remote Activation Test" on page 7

.

Installation and Termination of the ALCR-DIN

The ALCR-DIN is designed to attach to lighting control panels or electrical enclosures 
that are fitted with DIN-rail (compatible with DIN43880 and EN60715).

• Screw terminal connectors are provided on the unit for connection of normal sense 

and emergency power wires.

• Another screw terminal connector is provided on the bottom of the unit including four 

screw terminals: 

• A wire loop (jumper) is factory installed into two terminals and allows connection to a 

remote triggering device (dry contact, normally closed for fire alarms, test switch, etc.). 
When the normally closed contact is triggered, the contact input will open, activating the 
emergency lighting On.

• The remaining two screw terminals allow termination of 0-10V / Fluorescent lighting 

control. 

N o t e :

The remote triggering device, a test switch or an emergency system (fire alarm 

panel or security system) must be installed within 1,000 feet of the ALCR when 

using 18AWG wire.

N o t e :

ETC highly recommends that you power up and test your system before 

connecting to a remote device.

Do not cut the factory installed jumper unless you are installing a remote 

triggering device.

Summary of Contents for ALCR-DIN

Page 1: ...rol Relay ALCR is a UL 924 listed device that is powered from an emergency source and provides power to emergency lighting load s The ALCR ensures a lights on state during loss of normal power while t...

Page 2: ...DIN rail 35mm complies with DIN43880 and EN60715 Reference Installation and Termination of the ALCR DIN on page 4 Once installation of the Automatic Load Control Relay is complete reference Configurat...

Page 3: ...s to the normal lighting circuit as shown b Connect the Normal Neutral White 18 AWG lead to the normal Neutral for the lighting loads Step 6 Proceed to Initial Test on page 7 Step 7 If you are install...

Page 4: ...single pole contacts on the remote device or test switch Step 3 Continue to Remote Activation Test on page 7 Installation and Termination of the ALCR DIN The ALCR DIN is designed to attach to lighting...

Page 5: ...ch Sense and Normal Neutral screw terminals as shown Step 4 If you are connecting to 0 10 Vdc Fluorescent lighting loads connect to the provided terminals labeled 0 10V FLO Reference Examples of Use o...

Page 6: ...a user configurable delay time between regaining normal power and removing power from the emergency lighting This delay time could be used to account for loads that may require a warm up time for exam...

Page 7: ...f reconnect the Normal Power Switch wire to the terminal Step 6 Turn On the normal circuit breaker The ALCR should now behave as described in the Examples of Use on page 8 Step 7 If you are installing...

Page 8: ...gency Light Fixture ALCR Normal Neutral White Normal Hot Black Emergency Load Emergency Hot Emergency Neutral Gray Backup Arrangement When normal power is present the emergency load is turned off When...

Reviews: