E T C   I n s t a l l a t i o n   G u i d e

Automatic Load Control Relay

Automatic  Load  Control  Relay

Page 5 of 8

Electronic Theatre Controls, Inc.

Step 1:

Snap the unit onto the installed DIN-rail in the upright position at least 2” (5cm) 
away from any heat-generating devices. Refer to the label text as a guide. 
Tension clips on the unit provide an audible click that can be heard when the unit 
is installed properly.

Step 2:

Terminate the ALCR-DIN to the emergency lighting for the area controlled as 
shown in the wiring diagram on the previous page.
a:

Connect Emergency Power In and Out wires to the screw terminals on the 
unit in series with the emergency lighting as shown.

b:

Connect the Neutral for the emergency circuit to the Emergency Neutral 
screw terminal as shown.

Step 3:

Connect the ALCR-DIN to the normal lighting and control device for the area 
controlled. Reference the wiring diagram on the previous page.
a:

Connect the normal lighting circuit to the Normal Power Sense, Normal 
Switch Sense, and Normal Neutral screw terminals as shown.

Step 4:

If you are connecting to 0-10 Vdc / Fluorescent lighting loads, connect to the 
provided terminals, labeled 0-10V/ FLO. Reference 

"Examples of Use" on page 8

.

 

Step 5:

Continue to 

"Initial Test" on page 7

.

Step 6:

If you are installing a remote triggering device to remotely activate the emergency 
circuit On, return to this

"Installing a Remote Activation Input to the ALCR-DIN"

 for 

wiring instructions.

N o t e :

Follow all local code requirements for terminating wiring.

N o t e :

To ensure the emergency lighting connected to the device turns On in the event 

of a power loss, you must connect the Normal Power Sense wire on the line 

side of (before) any control device for the normal lighting loads.

NORMALLY

 

CLOSED

TEST

 

SWITCH

FIRE

 

ALARM

 

PANEL

SECURITY

 

SYSTEM

A

UTOMATED

 L

OAD

 

C

ONTROL

 R

ELAY

(ALCR-DIN)

Status 

LED

Option 

Button

Remote 

LED

NORMAL

 

SWITCH

 

SENSE

NORMAL

 

NEUTRAL

NORMAL

 

POWER

 

SENSE

EMERGENCY

 

POWER

 

OUT

EMERGENCY

 

POWER

 

IN

EMERGENCY

 

NEUTRAL

0-10V /

FLO

Remote

Loop

Emergency

Out

Neutral

In

Normal

Switch

Sense

Neutral

NOTE: Terminals 

accept a single wire 

12-30AWG.

Reference 

"Examples of Use" on 

page 8

 for possible installation 

layouts. 

Summary of Contents for ALCR-DIN

Page 1: ...rol Relay ALCR is a UL 924 listed device that is powered from an emergency source and provides power to emergency lighting load s The ALCR ensures a lights on state during loss of normal power while t...

Page 2: ...DIN rail 35mm complies with DIN43880 and EN60715 Reference Installation and Termination of the ALCR DIN on page 4 Once installation of the Automatic Load Control Relay is complete reference Configurat...

Page 3: ...s to the normal lighting circuit as shown b Connect the Normal Neutral White 18 AWG lead to the normal Neutral for the lighting loads Step 6 Proceed to Initial Test on page 7 Step 7 If you are install...

Page 4: ...single pole contacts on the remote device or test switch Step 3 Continue to Remote Activation Test on page 7 Installation and Termination of the ALCR DIN The ALCR DIN is designed to attach to lighting...

Page 5: ...ch Sense and Normal Neutral screw terminals as shown Step 4 If you are connecting to 0 10 Vdc Fluorescent lighting loads connect to the provided terminals labeled 0 10V FLO Reference Examples of Use o...

Page 6: ...a user configurable delay time between regaining normal power and removing power from the emergency lighting This delay time could be used to account for loads that may require a warm up time for exam...

Page 7: ...f reconnect the Normal Power Switch wire to the terminal Step 6 Turn On the normal circuit breaker The ALCR should now behave as described in the Examples of Use on page 8 Step 7 If you are installing...

Page 8: ...gency Light Fixture ALCR Normal Neutral White Normal Hot Black Emergency Load Emergency Hot Emergency Neutral Gray Backup Arrangement When normal power is present the emergency load is turned off When...

Reviews: