38
www.eta.co.at
Serial buffer connection
Buffer storage tank
8.6
Serial buffer connection
Serial buffer connection
If there are different buffer types, or if not all buffers can be set up in one group, serial connection of the buffers will
be necessary. Note that for serial buffer connection, integration of a solar heating system will work adequately only
when a fresh water module is used for the hot water supply.
Solar tanks with internal solar exchangers are only of limited effectiveness. Combination tanks with immersed hot
water tanks or internal water heat exchangers are unsuitable for a serial buffer connection. To minimize pipe
circulation losses, it is helpful to make the connections with downward siphon loops.
With fresh water module
1
Fresh water module flow
2
Temperature sensor [Sensor 1 (upper)]
3
Boiler, heating circuits, oil/gas boiler flow
4
Temperature sensor [Sensor 2]
5
Oil/gas boiler return
6
Solar flow
7
Temperature sensor [Sensor 3]
8
Solar return
9
Fresh water module return
10 Temperature sensor [Sensor 4]
11 Boiler and heating circuits return
maximum total output
Number of buffers
Connecting line, minimum
30 kW
4
DN 25
R 1"
28 x 1.5
50 kW
4
DN32
R 1¼"
35 x 1.5
65 kW
2
DN32
R1¼"
35 x 1.5
80 kW
4
DN 40
R1½"
42 x 1.5
Summary of Contents for PelletsCompact PC33
Page 1: ...2020 07 21 EN 0000000171 V 025 2707 93113 005 PelletsCompact 33 50 kW Installation...
Page 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33...
Page 51: ...Installation Network connection 51...
Page 55: ...Electrical connections Overview of circuit boards 55...
Page 74: ...www eta co at...
Page 75: ......
Page 76: ...www eta co at www eta co at downloads DOWNLOAD...