General information
Buffer storage tank
Buffers for multi-boiler systems
For systems with several boilers and also for those
with several very different heating circuits (especially
different times of operation or air and underfloor
heating in the same heating system), a bypass is
needed between heat producers and consumers to
ensure stable hydraulic conditions for the individual
circuits. A hydraulic bypass is nothing more than a pipe
connection between the flow and the return with the
same diameter as both. The differential water
quantities from heating and boiler circuits flow through
this bypass, This results in a neutral pressure point that
ensures that the heating circulation cannot influence
the boiler water circulation and vice versa.
A bypass that can do more than just stabilise pressure
conditions is the buffer. If a wood boiler for the base-
load range and an oil/gas boiler for peak load or as
emergency reserve are operated together in a heating
system, a buffer storage tank reduces the operating
time of the peak-load boiler by compensating for brief
differences between production and consumption. The
number of boiler starts/stops when consumption
fluctuates around the rated output of a boiler is
reduced, saving energy and easing stress on the
boiler.
To work as an output compensator and bypass for
several boilers, the buffer's storage capacity should be
chosen to match 20 to 30 minutes of full-load operation
for the largest automatic wood boiler in the system. In
special cases, peak loads and non-continuously
operated air heating systems must also be taken into
account, or the morning peak if the start of an oil/gas
boiler is to be avoided. Whereby "first", the morning
peaks themselves should be minimised with staggered
starting times for the heating circuits as well as
reasonable set-back temperatures.
Switzerland: Air Quality Control Regulation
In Switzerland, the Air Quality Control Regulation
"LVR" requires that heating boilers have a minimum
volume for heat accumulators (buffer). For the calcula-
tion, a distinction is made between manually and auto-
matically operated boilers.
•
For a manually operated boiler (e.g., log boiler) up
to 500 kW rated capacity, there needs to be at
least 12 litres of buffer volume for each litre of fuel
filling chamber. The volume must not exceed
55 litres per kW rated capacity.
Which is why a SH30 boiler (150 litres filling
chamber) needs a buffer volume of 1800 litres
(=150x12). A SH60 (223 l filling chamber,
223x12=2676 l) requires at least 3300 litres
(=60x55) buffer volume.
•
An automatic heating boiler up to 500 kW rated
capacity requires a minimum buffer volume of
25 litres per kW rated capacity.
Hence, a wood chip boiler with 100 kW needs a
minimum buffer volume of 2500 l (=100x25).
However,pellet boilers up to 70 kW rated
thermal input are exempt from this regulation.
Summary of Contents for PelletsCompact PC33
Page 1: ...2020 07 21 EN 0000000171 V 025 2707 93113 005 PelletsCompact 33 50 kW Installation...
Page 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33...
Page 51: ...Installation Network connection 51...
Page 55: ...Electrical connections Overview of circuit boards 55...
Page 74: ...www eta co at...
Page 75: ......
Page 76: ...www eta co at www eta co at downloads DOWNLOAD...