56
www.eta.co.at
[Heating circuit] function block
ETAtouch controller
5.6.3.2
Setting the heating limits
Specifying the heating limits for the heating circuit
For each heating circuit, separate heating limits are
adjustable for heating mode (within the set heating
times) and reduced operation mode (outside the set
heating times).
If the current outside temperature exceeds the
configured heating temperature (for example 18 °C),
the heating circuit is switched off. The same applies to
reduced-temperature mode as soon as the outdoor
temperature exceeds the set heating limit.
If the outside temperature falls below the set
heating limit (for example: 18 °C), a hysteresis of
2 °C will be observed in order to avoid cycling the
heating circuit. Accordingly, the heating circuit will
switch on only once the outside temperature falls
below 16 °C (=18 °C - 2 °C).
The heating limits are adjusted through the settings of
the heating circuit (
button) in the heating curve
menu (
button).
Setting heating limits for heating mode
1. Change the selector switch to the heating mode
position (
).
Use the arrow keys to reduce parameter [Heating
threshold], so that the heating circuit in heating
mode switches off at a lower outside temperature,
or increase the value.
Fig. 5-54: Heating threshold for heating mode
Setting heating limits for the reduced operation
mode
1. Change the selector switch to the reduced
operation mode position (
).
Use the arrow keys to reduce parameter [Heating
threshold], so that the heating circuit in reduced
operation mode switches off at a lower outside
temperature, or increase the value.
At settings below 0 °C, there is a risk of
freezing.
Fig. 5-55: Heating limit for reduced-temperature mode
Summary of Contents for PelletsCompact 20-32 kW
Page 1: ...2017 04 19 EN 0000000282 V 003 3 38 1 1910 93108 002 PelletsCompact 20 32 kW Operation...
Page 27: ...ETAtouch controller Getting to know the control system 27...
Page 31: ...ETAtouch controller Boiler function block PelletsCompact 20 32 kW 31...
Page 41: ...ETAtouch controller Buffer function block 41...
Page 45: ...ETAtouch controller Hot water tank function block 45...
Page 49: ...ETAtouch controller Fresh water module function block 49...
Page 63: ...ETAtouch controller Solar function block 63...
Page 67: ...ETAtouch controller Pellet store function block 67...
Page 74: ...www eta co at...
Page 75: ......
Page 76: ...www eta co at www eta co at downloads DOWNLOAD...