Cleaning and maintenance
Maintenance table
7
2.3
Maintenance table
Cleaning must be carried out at least once a year or when requested by the control system. Maintenance is
necessary at least every 2 years or when requested by the control system. We recommend you perform
maintenance annually.
Tasks
Regular
ly
Cleaning
annually
Maintenan
ce
at least
every 2
years
to be
performed by
Emptying ash bin
•
Emptying ash bin
•
Check the seals
X
X
X
Customer
Clean the piping
•
Clean the piping between the boiler, precipitator and
chimney
X
X
Customer or
specialist
Clean the precipitator
•
Check and remove ash accumulations
•
Clean the flushing air opening
•
Clean and inspect the electrode holder
•
Check the alignment of the electrodes
•
Check maintenance cover seal
X
X
Customer or
specialist
Check flaps
•
Check the drive chain of the flaps
•
Check the positions of the flaps and position switch
•
Check the seals on the flaps
X
Specialist
Check the electrode cleaning
•
Check the drive chains and position switches of the
electrode dedusting
•
Check idle position of the electrode dedusting
•
Checking the ease of movement of the striking
mechanisms
X
Specialist
Check de-ashing
•
Check the drive chains and position switches of the
electrode dedusting
•
Check the drive chains and the position switches of both
sliding rakes
X
Specialist
Clean flushing air fan
X
Specialist
Check the safety switch for the maintenance cover
X
Specialist
Check the safety switch for the ash bin
X
Specialist