6 Technical Data
page 65
ELC X-Series-V1.5-06.18-GB
subject to technical alterations
Mechanical characteristics
Type
ELC X12-110
ELC X12F-110
ELC X12B-110
ELC X12i-110
Dimensions
(approx. H x W x D)
125 x 470 (±1mm) x 420 mm
Weight (approx.)
20.5 kg
21.1 kg
20.5 kg
Installation position
horizontal as described in 3.1
Control characteristics
Type
ELC X12-110
ELC X12F-110
ELC X12B-110
ELC X12i-110
Current requirement of 24V-
supply (X805.5)
2.2 A max. For ELC control circuitry
2.7 A max. For ELC
control circuitry
Output currents of X806 Pins 5 + 6 have to be added
Baud rate
PROFIBUS: 500kBit
MODBUS: Baud rate 19200, 8 Databits, even
parity, 1 Start/Stop Bit
- -
Modbus timeout
60 s
- -
Max. number of devices per
BUS segment
recommended with PROFIBUS: 40
when operating in compliance with
ANSI/EIA/TIA-485-A-98: 50
- -
Ambient conditions
Type
ELC X12-110
ELC X12F-110
ELC X12B-110
ELC X12i-110
Humidity
max. 85%, non-
condensing
max. 95%
max. 85%, non-
condensing
Ambient operation temperature
5°C to +45°C
0°C to +55°C
5°C to +45°C
Ambient storage temperature
-20°C to +70°C during storage and transportation, before initial
operation leave at least 4 hrs at room temperature
Maximum storage period
2 years (also see paragraph 4.2)
Air flow
max. 200 m³ / h at T_A >35°C
typ. 100 m³ / h
Altitude of site
max. 4000 m above sea level
up to 2000 m above sea level without derating
2000 m to 4000 m above sea level: 1.5% / 100 m power reduction
effected by ELC-control (8400 W at 4000 m above sea level)