3 Installation
page 4
ELC X-Series-V1.5-06.18-GB
subject to technical alterations
3
Installation
3.1
Mounting of casing
The ELC may only be installed as described in 3.1.1 and in 3.1.2, allowing for at
least
the
minimum
spacing
as
shown
in
Horizontal mounting upside down is not allowed. All vertical mounting
orientations are possible.
The ELC should not be mounted in the immediate proximity of sensitive electronic
equipment. An appropriate distance must be maintained to scatter field
transformers or other inductors.
The ELC is equipped with built-in fans to ensure forced air cooling. Air ducts and
optional filters must be designed to allow the air flow described in chapter 6. The
ambient temperature must not exceed the values described in chapter 6. The
ambient temperature is measured by the ELC and will be stored within the
internal error memory.
3.1.1
Mounting of single ELC
The side surfaces of the housing contain 2 T-slots each. Fig. 1 indicates the relative interspace
of the two T-slots and distance to the outer face of the housing. The T-slots are suitable for
sliding blocks 6mm groove, M5 by Bosch Rexroth, as well as for sliding profiles (see Fig. 2) ,
the latter applicable for X6 and higher power, both available as accessories. Fig. 3 shows the
horizontal mounting orientation including the minimum spacing at the back of the ELC.
Alternatively the ELC may be mounted flush with the rear panel if a cut out for the ventilation
is ensured.
Fig. 1:
Position of the T-slots
Fig. 2:
Sliding profile