NOTE: When turning the LUX control (starting from the moon symbol),
if the current ambient light value is reached, the red LED will light up (as
a setting aid). The LED will automatically go out after 30 seconds.
: “short pulse” function for light channels C1/C2
Once the detector has been triggered by movement (lighting is below
preset ambient lighting level), the lighting and the
red LED
will be
switched on for 1 second and then off for 9 seconds.
: “short pulse” function for channel C3 (HVAC)
Once the detector has been triggered by movement, the channel
and the
green LED
will be switched on for 5 seconds and then off for
5 seconds.
Field of detection "test" function
The connected lighting is switched on - immediate, load-free indication
of movement given by 2 short flashes of the
blue LED
(blue mode).
DIP switch 2: fully automatic (A)/semi-automatic (M)
DIP switch 2
is only active if
DIP switch 1
has been switched to manual!
Whichever option you choose affects C1, C2 and C3. For a detailed
description of fully automatic/semi-automatic mode,
please refer to
chapter 7 "Functions"
.
DIP switch 3: Standard/corridor function:
ON/OFF = standard function
The lighting can also be switched on and offf using an external button.
ON = corridor function
The lighting can only be switched on using an external button.
DIP switch 4: Adjusting the sensitivity
The device is set to maximum sensitivity
"S-max."
in the factory
settings. If the switch is set to
"S-min."
, the level of sensitivity is
reduced. This setting is recommended if undesired switching occurs
due to interference sources, such as hot air streams.
7 • FUNCTIONS
Fully automatic mode
Light channels C1 + C2
will switch on automatically, depending on the
preset light value and detection of movement. They will remain on
for as long as movement is detected and as long as the ambient light
value does not exceed the preset light value. The
HVAC channel C3
is
switched on when movement is detected, regardless of the ambient
light value. The time settings for the respective channels will start if
movement is no longer detected. Each channel can also be manually
switched on or off using
buttons S1 - S3
. The device is preset to fully
automatic mode.
Semi-automatic mode for light channel C1 + C2
Switched ON/OFF manually using the
S1 or S2 button
. They will remain
on for as long as movement is detected and as long as the ambient
light value does not exceed the preset light value.
Semi-automatic mode for HVAC channel C3
Switched ON/OFF using the
S3 button
. If movement is no longer
detected, the time setting for
C3
will start and the lighting will switch
off once the set time has elapsed.