4.11 Other Output Signals
4.11.1 Servo alarm output
The following diagram shows the right way to connect the Alarm Output.
I/O Power supply
+24V
Servo drive
7
8
ALM+
ALM-
0V
1CN
50mA max
Optocoupler output
(Each output node)
Max.output voltage: 30V
Max.output current: 50mA
An ex24V I/O power supply is required since there is no +24V power source available inside the servo drive.
Output → ALM+ 1CN- 7
Servo alarm output
Output → ALM- 1CN- 8
Servo alarm output uses grounding signal
ALM outputs a signal when the servo drive is detected in an abnormal state.
Be detected
abnormal
Servo drive
ALM Output
Cut off the main circuit
power
Normally, the external circuit consists of /ALM should be able to switch off the power of servo drive.
Signal
Status
Output level
Comments
ALM
ON
ProNet-
□□□
MG: CN1_07, CN1_08:
“L” level
ProNet-
□□□
EG-EC: CN1_12, CN1_14:
“L” level
Normal state
OFF
ProNet-
□□□
MG: CN1_07, CN1_08:
“H” level
ProNet-
□□□
EG-EC: CN1_12, CN1_14:
“H” level
Alarm state
When “servo alarm(ALM)” happens, always remove alarm reasons first , and then turn the input signal "/ALM-RST" to ON
position to reset alarm status.
→ Input/ALM-RST 1CN- 39
alarm reset input
Signal
Status
Input level
Comments
/ALM-RST
ON
ProNet-
□□□
MG: CN1_39:
“L” level
ProNet-
□□□
EG-EC: CN1_19:
“L” level
Reset servo alarm
OFF
ProNet-
□□□
MG: CN1_39:
“H” level
ProNet-
□□□
EG-EC: CN1_19:
“H” level
Do not reset servo alarm
Normally, the external circuit can switch off the power supply of the servo drive when an alarm occurs. When
powered on again, the servo drive removes the alarm automatically, so the alarm reset is not required to be connected. In
addition, the alarm reset is enabled with the panel operator.
Note: When an alarm occurs, remove the alarm reason before resetting the alarms.