CAUTION
: This procedure completely erases the memory and
restores factory defaults!!! Once the memory is cleared, all pro-
grammed User Codes are erased and factory default settings are
restored.
1. Remove power.
2. Jumper the two pins above the connector labeled “CONFIG.”
3. Apply appropriate power. (You should hear 4 beeps and the
RED LED will flash and the GREEN LED will be solid).
4. Once the Keypad is in configuration mode, enter 0099#. The
Keypad will beep twice and both LEDs will flash for approxi-
mately 10 seconds. (During this time, the Keypad will appear
dead. Do NOT remove power!!!)
5. Wait and you will hear 4 beeps and the RED LED will flash and
the GREEN LED will be solid.
6. Enter the configuration number followed by #.
a. Keypad Output
Keypad Output
Configuration
Self-Contained - Non-encoded
99 #
b. (OPTIONAL) To change the audible beep, enter
Code Audible Beep
201 # Normal Beep (factory default)
200 # Short Click (quieter)