![ESP EnVision EV-12010 BR User Manual Download Page 34](http://html1.mh-extra.com/html/esp/envision-ev-12010-br/envision-ev-12010-br_user-manual_2427537034.webp)
User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / ametekesp.com
33
Parameter
Specification
Under-Voltage
Shutdown
120V Models
Adjustable from 0 V to 110 V. Default 80 V.
208-240V Models
Adjustable from 0 V to 220 V. Default 160 V.
Under-Voltage Record
120V Models
Adjustable from 0 V to 110 V. Default 100 V.
208-240V Models
Adjustable from 0 V to 220 V. Default 180 V.
Under-Voltage Restore
120V Models
Adjustable from 80 V to 110 V. Default 105V.
208-240V Models
Adjustable from 80 V to 220 V. Default 190 V.
Over-Voltage Shutdown
120V Models
Adjustable from 130 V to 160 V. Default 150 V.
208-240V Models
Adjustable from 220 V to 300 V *. Default 280 V.
Over-Voltage Record
120V Models
Adjustable from 130 V to 160 V. Default 145 V.
208-240V Models
Adjustable from 220 V to 300 V *. Default 270 V.
Over-Voltage Restore
120V Models
Adjustable from 130 V to 160 V. Default 140 V.
208-240V Models
Adjustable from 220 V to 300 V *. Default 260 V.
Internal Memory Capacity
512 Power Quality Events with Timestamp
138 Day Electrical Parameter History at 30 minute intervals
2.25 Day Electrical Parameters at 10 second intervals
Timestamp Accuracy
± 1% Typical Product Accuracy
Measurement Accuracy
120V Models
± 2% Typical product accuracy
208-240V Models
± 2% Typical product accuracy
Response Time
Over-Voltage
90 ms
Under-Voltage
200 ms
Power Outage Event Definition
AC Voltage has dropped below 20V
Surge Event Definition
Filter has been exposed to a transient voltage in one of the 3
possible modes (between Live and Neutral, between Live and
Ground, between Neutral and Ground) with a peak amplitude of
500V
*
or higher and a frequency of 20 kHz or higher.
*500V surge
voltage amplitude applies to IEEE C62.41 Category B Impulse;
surge voltage amplitudes necessary for detection of other surge
types may vary.
Modem/Fax Protection
Single telephone line surge suppression
Ethernet Protection
CAT6 network surge protection
Dimensions
10-20A Models
6.125” W x 8.375” D x 2” H
30A Models
7.75” W x 4” D x 11.25” H
Weight
10-20A Models
2.25 lbs.
30A Models
10 lbs.
Temperature Range
5C to 35C
Humidity Range
5% to 95% R.H. Non-condensing
Agency Listings
EV-12015
EV-12020
EV-20815
EV-20820
EV-20830-(L)630(-GNS)
ETL Certified to UL 1449 3rd Edition
ETL Certified to UL 1283 5th Edition
ETL Certified to CSA 22.2 No. 8-M1986 (R2008)
EV-12010 BR
EV-12016 BR
EV-20816 BR
Tested per UL1449,4th Ed.,Dated August 20,2014
EV-23010
EV-23016
EV-23016-F
EV-23030-GNS
TUV Certified to IEC 60950-1:2005 (Second Edition) + Am 1:2009 +
Am 2:2013
* The allowed range was changed from 260-300V to 220-300V in firmware version 1.JB3,
released in December 2016.
** Specifications subject to change without notice
** All listed specifications obtained at an ambient temperature of 25°C