background image

EsiWelma Srl

 

URS20SL_en.doc - rev. 0 

Oxygen detectors – URS20SL 

20/10/2010 

Gas detection systems for industrial environments 

7/8

 

 

Checklist after 
mechanical and 
electrical installation 
(continued)

 

Since the sensor scale is  between  0…...30% O

2

,  in  air (20.9% O

2

) the 4…...20mA 

output must be set between 14 and 16mA (theoretic value 15.1mA). 

Use  the  calibration  kit  to  apply  the  gas  mixture  at  4%  of  CO

2

,  making  sure  the 

4...20mA output is between 5 and 7mA (theoretic value 6.1mA); the status LED and 
the pre-alarm, 1

st

 and 2

nd

 alarm threshold relays on the optional relay card switch on 

according to the thresholds and the alarm mode settings. 
 

Maintenance 

Routine 
 

Corrective 

 
 
 
 
 
 
 

Decommissioning

 

A sensor functional test should be carried out every three-six months. 

Routine  maintenance  involves  repeating  the  same  tests  as  set  forth  in  “checklist 
after mechanical and electrical installation”. 

If any abnormalities are found during routine sensor maintenance, return the sensor 
concerned  to  the  supplier  /  installer,  who  in  turn  will  send  it  back  to  the 
manufacturer. 
Sensors  may  need  to  be  re-calibrated,  using  the  TUL40..  calibration  kit  and  the 
TUS40-20  handheld  terminal,  which  must  be  connected  to  the  sensor  via  the 
communication interface integrated in the cable (on the connector CN4). 

 

For  the  re-calibration  procedure,  see  the  instructions  supplied  with  the  handheld 
terminal. 

Remove power from the detector, disconnect all  wiring and conduits and dismount 
the housing from all the blocking systems. 
 

Warranty 

Warranty  on  EsiWelma  products  is  valid  for  12  months  from  installation  date  and 
no  longer  than  24  months  from  manufacturing  date  on  the  product.  Installation 
data,  stamp  and  signature  on  the  data  sheet  filled  in  by  the  installer  will  be 
considered proof for warranty. 

 

A copy of the warranty data sheet must be sent when returning the product under 
warranty. 

 

Accessories 

UZR20.4 Four-relay card 
TUL40.. Gas calibration Kit 
TUS40 Handheld terminal 
CRG40 Gas collecting cone 
PAP40 Powerful jets protection 
 

Dimensions and weight 

 

Dimensions (HxWxD): 130x100x60mm.                                                Weight: 0.5Kg 

 

 

 

Summary of Contents for Sensigas URS20SL

Page 1: ...d more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SL sensors can be u...

Page 2: ...t 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1 st threshold alarm 20mA 2 nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up...

Page 3: ...the excess oxygen as quickly as possible Oxygen deficiency Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other gases that deplete the oxygen in the air theref...

Page 4: ...chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in part...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection...

Page 6: ...trical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended...

Page 7: ...ntenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 h...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Reviews: