Oxygen detectors – URS20SL 

20/10/2010 

Gas detection systems for industrial environments 

3/8

 

 

Sensors lifetime 

Sensor average lifetime (see technical characteristics) is referred to a typical usage 
in  a  pollution-free  environment.  Presence  of  a  high  concentration  of  pollutants  can 
shorten the lifetime of the sensing element. 

Once the detection system starts up, it has to be supplied with energy during all the 
lifetime of its sensors. 

Seasonal use of the detection system is not recommended. 

 

Installation 

 

Oxygen excess 

Since oxygen weighs more or less the same as air, unless there is forced or natural air 
circulation, it tends to spread at the point of the leak. 
So,  the  excess  oxygen  detectors  must  be  installed  near  any  likely  leakage  points,  in 
order to detect the excess oxygen as quickly as possible. 

 

Oxygen deficiency 

Detection  of  oxygen  deficiency  has  the  purpose  of  indirectly  detecting  the  presence  of 
other gases that deplete the oxygen in the air, therefore causing asphyxiation problems, 
for example. 
In this case, the detectors must be located at the breathing height of the occupants in the 
premises. 

 

 

Take into consideration the following specific installation guidelines, as well as the above 
instructions, for location of the detectors. 

The detectors must be installed: 

1.  where accidental gas leakages are possible 
2.  at least 1.5m away from heat sources or from vent holes 
3.  not in spaces where ventilation is poor and where gas pockets may form 
4.  away from hindrances to natural gas flow 
5.  away from equipment that may leak gas during normal operations 
6.  in  environments  with  a  temperature  range  of  -20°C  to  50°C  and  relative  humidity 

below 90% (non-condensing) 

7.  Disconnect  equipment  from  the  power  supply  when  mounting  and  dismantling 

detectors. 

 

Summary of Contents for Sensigas URS20SL

Page 1: ...d more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SL sensors can be u...

Page 2: ...t 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1 st threshold alarm 20mA 2 nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up...

Page 3: ...the excess oxygen as quickly as possible Oxygen deficiency Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other gases that deplete the oxygen in the air theref...

Page 4: ...chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in part...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection...

Page 6: ...trical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended...

Page 7: ...ntenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 h...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Reviews: