EsiWelma Srl

 

URS20SL_en.doc - rev. 0 

Oxygen detectors – URS20SL 

20/10/2010 

Gas detection systems for industrial environments 

2/8

 

 

Technical 
characteristics 

 

Type of sensor 

Electrochemical cell 

Detectable Gas 

 

O

2  

excess 

 

O

2

 deficiency 

Power supply 

11÷28Vdc 

Max power consumption 

2.5W 

Measuring range  

0…30% O

2

 

Precision 

±

 2,5% of full scale range (in air) 

Repeatability 

±

 2,5% of full scale range 

Measurement resolution 

0.1% O

2

 

Microprocessor resolution 

1024 points (10 bit) 

Digital filter system 

Kalman Filter 

Watchdog 

Internal 

Warm-up time 

< 2m 

Stabilization time 

< 2m 

Response time 

< 10s (T20), < 45s (T90) 

Average Sensor life (in air) 

120 weeks 

Sensor type settings 
(O

2

 excess or deficiency) 

S1.7 DIP switch 

OFF (O

2

 excess) 

S1.7 DIP switch 

ON (O

2

 deficiency) 

Threshold limit settings  

(S1.8 = OFF, default): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

23% O

2

 

25% O

2

 

27% O

2

 

 
 

19% O

2

 

17% O

2

 

15% O

2

 

Threshold limit settings  
(S1.8 = ON): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

22% O

2

 

23% O

2

 

24% O

2

 

 
 

20% O

2

 

19% O

2

 

18% O

2

 

4..20mA Output 

Proportional mode 
(default) 

 

Consumption mode 
(applications at 1 or 2 
thresholds) 
4…20mA Output reference 
selection: 

 
-   4mA   =    0% O

2

 

- 20mA   = 30% O

2

 

 
-   0mA   = no alarm 
- 10mA   = 1

st

  threshold alarm 

- 20mA   = 2

nd

  threshold alarm 

 
by jumper selectable polarity 

4…20mA output load resistor 

- up to 200

 at 12Vdc power supply 

- 200

 

÷

 700

 at 24Vdc power supply 

Operating Temperature 
Storage Temperature 

-20 

÷

 50 °C 

-20 

÷

 70 °C 

Relative Humidity (without condensing) 

-

  Operation 

-

  Storage 

 

 

15 

÷

 90 %RH 

45 

÷

 75 %RH 

Operating pressure (KPa) 

80 

÷

 110 

Air speed (m/s) 

 6 

Visual warnings 

Red LED visible with detector energised 

Dimensions and weight 

See dedicated section 

Options & Accessories 

 

Card with 4 SPDT relays UZR20.4 

NO or NC contacts available, jumper 
selectable 

See threshold limit settings 

Maximum relay capacity: 

50mA at 24Vac/dc, 100mA at 12Vac/dc 

Relay operating mode: 

-

 

direct: relay ON when an event is detected 

-

 

reverse: relay ON when no event is 
detected 

TUL40.. Gas calibration kit 

See installation and commissioning chapter 

TUS40 Handheld terminal for service and 
maintenance 

See installation and commissioning chapter 

CRG40 gas collecting cone 

See dedicated data sheet 

PAP40deluge protection 

See dedicated data sheet 

 
EC Conformity 
EMC Directives / Standards, 
 
LVD Directives / Standards 

 
 
Electromagnetic  Compatibility  Directive  EMC 
2004/108/EC, Standard EN50270 
Not applicable 

 

Summary of Contents for Sensigas URS20SL

Page 1: ...d more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SL sensors can be u...

Page 2: ...t 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1 st threshold alarm 20mA 2 nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up...

Page 3: ...the excess oxygen as quickly as possible Oxygen deficiency Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other gases that deplete the oxygen in the air theref...

Page 4: ...chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in part...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection...

Page 6: ...trical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended...

Page 7: ...ntenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 h...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...