Oxygen detectors – URS20SL 

20/10/2010 

Gas detection systems for industrial environments 

4/8

 

 

Electrical Installation 

 
 
 
 
 
 
 
 

Terminal board and 
electrical connections 
 
 
 
 
 
 
 
 
 
 

Cabling:

 

 
 
 

 

Configuration: 

 
 
 

 

4…20mA Output 
reference selection: 
 
 
 
 
 
 
4...20mA signal 
operating mode 
configuration: 
 
 

 

Setting threshold limit 
values: 
 

CAUTION:  

 Make the area safe and make sure that the device power supply is 

off before cabling and configuration operations. 

Install the sensor in compliance with laws in force. 
The cable gland provided on the housing is used for cable entry. 
Ground the sensor using the internal grounding system. 

 
Ground connection 
 

Terminal board TB1 

12…24Vdc 

4…20mA 

 
JP2 jumper circuit 

 

Dip-Switch S1 

  

CN4 connection for  
handheld terminal 

 

 
 

 

Depending  on  the  connecting  distance,  use  at  least  3-core  cable,  min.  diameter 
0.75mm

2

 up to 100m, 1mm

2

 up to 200m, 1.5mm

2

 up to 500m. 

Use shielded cable where there is a risk of electromagnetic interference.  
If a relay card is used, use multi-core cable suitable for the number of connections. 

 

Default settings of the sensor are shown in the “Technical Specifications” chapter. 
In  order  to  change  the  default  settings,  switch  off  the  power  supply,  input  the  new 
settings at the JP2 jumper circuit or at the  S1 DIP switch as shown in the diagram, 
then power-up again; in particular: 

 

The  default  setting  for  the  4-20mA  signal  is  the  negative  power  signal.  Output 
reference selection should be made by JP2 triple of jumpers; to change this setting, 
operator has to move JP2 jumpers as shown in the figure: 

Caution:  if  the  default  settings  are  changed, 
the  connections  on  the  TB1  terminal  board 
will be inverted. 

     Ref. at  

-

  (default)            Ref. at    

++++

 

 

To  set  the  operating  mode  of  the  4...20mA  signal,  it  is  necessary  to  use  the  5th 
selector of the DIP switch at S1; in particular: 

 
 

 

                                            Proportional                        Threshold mode 

 

To  set  the  threshold  limit  values  of  the  optional  relay  card,  or  of  the  threshold 
operating mode of the 4...20mA signal, it is necessary to use the last selector of the 
DIP switch at S1 (ignore the first four selectors); in particular, the thresholds, given in 
percentage of O

2

, will be: 

 

 

 

 
(S1.8 = OFF, default): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

O

2

 excess

 

 

23% O

2

 

25% O

2

 

27% O

2

 

O

deficiency

 

 

19% O

2

 

17% O

2

 

15% O

2

 

 
(S1.8 = ON): 

Pre-alarm 

1

st

 threshold alarm 

2

nd

 threshold alarm 

 
 

22% O

2

 

23% O

2

 

24% O

2

 

 
 

20% O

2

 

19% O

2

 

18% O

2

 

Relay card

 

Sensor card 

Connection 
slot for relay
card

 

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

Summary of Contents for Sensigas URS20SL

Page 1: ...d more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SL sensors can be u...

Page 2: ...t 1 or 2 thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1 st threshold alarm 20mA 2 nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up...

Page 3: ...the excess oxygen as quickly as possible Oxygen deficiency Detection of oxygen deficiency has the purpose of indirectly detecting the presence of other gases that deplete the oxygen in the air theref...

Page 4: ...chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP switch as shown in the diagram then power up again in part...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection...

Page 6: ...trical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommended...

Page 7: ...ntenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 h...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Reviews: