6.2
Configuration
The operation starts from the status of the control unit and from the field devices left in
Chapter 5 and ends with the recognition by the control unit of all the field devices in the new
system. After powering up the system, the devices will show the following status:
•
CONTROL UNIT:
all relays energised (corresponding internal LEDs on)
•
SENSORS:
Status LED flashing rapidly
•
ALARM MODULES: all LEDs on and status LED flashing rapidly
•
RELAY MODULES:
all relays energized (corresponding LEDs on) and status LED
flashing rapidly
•
DISPLAY MODULES: display off and status LED flashing rapidly
NOTE
If a new system includes a field device already configured on another system, when
this is switched on, it self-excludes and takes its status LED to rapid flashing thus
getting ready to be configured once again
As already shown in paragraph 5.1, when the control unit is first switched on, “NEW
INSTALLATION” is automatically shown on the command line
IMPORTANT
For configuration we recommend following the order indicated in Table 3.1, filled in
CAUTION
The control unit automatically exits the configuration status 15 minutes after the
last time the key on a field device is pressed, or manually by pressing the key
BIP
N E W I N S T A L L A T I O N
* WA I T P L E A S E *
Fig. 6.6
Press down for 5 sec.
N E W I N S T A L L A T I O N
T O C O N F I R M
P R E S S - , + ,
S I MU L T A N E O U S L Y
Fig. 6.5
C O N F I G U R A T I O N ME N U
N E W I N S T A L L A T I O N
N E W C E N T R A L U N I T
D E L E T E D E V I C E
Fig. 6.4
N E W I N S T A L L A T I O N
S - - R M - - D M - - A M - -
P R E S S D E V I C E B U T T O N
Fig. 6.7