Manufacturer Specific Profile Area
Manual • Doc.-No.: C.3055.21 / Rev. 1.1
CAN-CBX-COM2
Page 114 of 125
8.12.2.13 Tx_Cycle_Time
An overview of the communication parameters 2800
h
and 2900
h
is shown on page 95.
Parameter name
Tx_Cycle_Time
Object index,
Sub-index
2800
h
, 0E
h
(COM A) /
2900
h
, 0E
h
(COM B)
Access mode
rw
Data type
unsigned 16
Value range
0000...FFFF
h
Unit
ms
Default value
0
Description:
For recurring transmission orders with the same content, as e.g. used for the
initialization of gauges on the serial bus, the CAN-CBM-COM2 module offers a
function for cyclic transmission of a programmable character string. The function
relieves the CAN bus because the character string must be sent to the CAN-CBM-
COM2 module only once.
The time for cyclic transmissions of the character string on the serial bus is set via
the parameter Tx_Cycle_Time. For Tx_Cycle_Time = ‘0’ no transmission will be
carried out.
The content of the character string is transmitted via the parameter Tx_Cycle_String
(object 2810
h
/2910
h
, see page 117) .