Activated Carbon Filter Replacement Procedure
The filter without condensate drain tube extending from the bottom of the filter housing is an activated carbon
filter. To replace the filter cartridge follow the steps below:
Step 7:
Remove the filter housing bowl by unscrewing it from the top portion of the filter housing which is
connected to the internal system piping.
Step 8:
Once the filter housing bowl has been removed, the filter cartridge inside is removed by first unscrewing
the black retaining disc at the base of the cartridge and then pulling down on the cartridge. Discard the
old filter cartridge and replace it with the appropriately marked filter cartridge from the maintenance kit
by pushing up so that it fits snugly onto the receiving stepped cylinder in the upper part of the filter
housing. Screw the black retaining disc back onto the central metal threaded rod.
Important: HAND TIGHTEN ONLY!
Step 9:
Replace the filter housing bowl by screwing it onto the filter housing top.
Important: HAND TIGHTEN ONLY!
Step 10:
Tighten the petcock valve to the closed position.
Step 11:
The ECS Protector Nitrogen Generator can now be placed back into service.
Return the ECS Protector Nitrogen Generator to Service
1.
Turn the power supply to the unit on.
2.
Open the inlet and outlet ball valves, and close the bypass valve on the bypass loop.
3.
Check inside the nitrogen generator cabinet for leaks using a soap water solution. Tighten fittings where
needed.
ECS Protector Nitrogen Generator Optional Monitoring Equipment
•
ECS Protector Handheld Gas Analyzer (PHGA
-
1)
: portable handheld gas analyzer includes one
-
button
calibration and enables user to measure nitrogen concentration at nitrogen generator cabinet or gas
sampling ports on ECS venting devices
•
ECS Protector SMART Gas Analyzer (SGA
-
1/1E)
: permanently installed near an ECS Protector Manual/
SMART Vent to continuously report nitrogen gas concentration to a building information or management
system; includes digital display and provides 0
-
5V DC or 4
-
20mA output signals
•
ECS In
-
Line Corrosion Detector (ILD
-
X)
: installed in
-
line within the fire sprinkler system piping at
locations most susceptible to corrosion; provides either a local push
-
button test/indicator or control
panel monitoring