ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) 

June 2018 - Rev 5 

Engineered Corrosion Solutions 

 11336 Lackland Road 

 St. Louis, MO 63146 

 Phone 1-314-432-1377 



www.ecscorrosion.com 

ECS Protector

 

Nitrogen Generator 

 

 

designed for fire sprinkler systems 

Typical ECS Protector Nitrogen Generator Dry/Preaction System Schematic

 

 

 

 

 

 

 

 

 

 

 

Maintenance of the ECS Protector Nitrogen Generator

 

The nitrogen cabinet contains three (3) separate cartridge filters. 

It is recommended that each filter be replaced 

as  part  of  an  annual  preventative  maintenance  program. 

In some environments it may be necessary to replace   

filters  more  frequently.  The  filter  kit  for  the  PGEN

-

30  (PGEN

-

30E)  is  part  number  PGEN

-

FKS.  When  maintained 

properly the nitrogen separation membrane will provide up to 20 years of service life.

 

Filter Replacement Procedure

 

Preliminary Steps (taking the nitrogen generator out of service)

 

1.

 

Turn the power supply to the unit off

 

2.

 

Close the inlet and outlet ball valves on the bypass loop

 

3.

 

Depressurize the nitrogen generator internal inlet piping by slowly unscrewing the petcock valve on the bottom 
of the leftmost filter housing 

 

Coalescing Filter Cartridge Replacement Procedure

 

The  filters with condensate  drain  tube  extending  from  the  bottom of  the  filter  housing  are  coalescing filters.  To 
replace the filter cartridges follow Steps 1 through 6 on the following page.

 

 
 
 
 
 
 
 
 
 
 
 

Clear Drain 

Nitrogen

 

Generator

 

Air Compressor

 

Dry/Preaction

 

Sprinkler Risers

 

ECS Protector Dry Pipe

 

Venting Device

 

Nitrogen/Air

 

Supply Line

 

Summary of Contents for PGEN-30

Page 1: ...acement Filters PGEN FKS Annual Maintenance Gas Membrane PGEN MS 20 Year Expected Service Life The ECS Protector Nitrogen Generator is designed for use in maintaining supervisory gas and facilitating...

Page 2: ...storage and manual bypass Power supply 120 VAC 1 phase 60Hz 230 VAC 1 phase 50Hz Single point nitrogen air discharge NPT Hour Run Meter Cycle Counter The ECS Nitrogen Generator includes the following...

Page 3: ...Power Supply The ECS Protector Nitrogen Generator requires a dedicated power supply to prevent interruption from other equipment The incoming power supply line ties into the top of the terminal block...

Page 4: ...ng where used The nitrogen generator cabinet has two 2 system signals and five 5 outputs that can be monitored by the facility s BMS or fire alarm system The nitrogen generator is operating in the byp...

Page 5: ...N 30E is part number PGEN FKS When maintained properly the nitrogen separation membrane will provide up to 20 years of service life Filter Replacement Procedure Preliminary Steps taking the nitrogen g...

Page 6: ...ce the filter housing bowl has been unscrewed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge Di...

Page 7: ...TIGHTEN ONLY Step 9 Replace the filter housing bowl by screwing it onto the filter housing top Important HAND TIGHTEN ONLY Step 10 Tighten the petcock valve to the closed position Step 11 The ECS Pro...

Page 8: ...N 10 PGEN 20 PGEN 30 PGEN 40 PGEN 50 PGEN 60 Total System Capacity 675 gal 950 gal 2 000 gal 3 200 gal 6 500 gal 11 000 gal 18 500 gal 22 500 gal Single System Capacity 40 psi 1 215 gal 265 gal 560 ga...