ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E)
June 2018 - Rev 5
Engineered Corrosion Solutions
11336 Lackland Road
St. Louis, MO 63146
Phone 1-314-432-1377
www.ecscorrosion.com
ECS Protector
Nitrogen Generator
designed for fire sprinkler systems
Step 1:
Grasp the ¼
”
clear drain tube on the bottom of the filter housing with the right hand. With the left hand,
push upward on the grey retaining ring on the filter housing outlet fitting. This will allow for the ¼
”
clear
drain tube to be removed from the fitting.
Step 2:
Once the ¼
”
clear drain tube has been disconnected, the filter housing bowl may be unscrewed from the
top portion of the filter housing which is connected to the internal system piping.
Step 3:
Once the filter housing bowl has been unscrewed, the filter cartridge inside is removed by first
unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge.
Discard the old filter cartridge and replace it with the appropriately marked filter cartridge from the
filter replacement kit by pushing up so that it fits snugly onto the receiving cylinder in the upper part of
the filter housing. Screw the black retaining disc back onto the central metal threaded rod.
Important: HAND TIGHTEN ONLY!
Step 4:
Replace the filter housing bowl by screwing it onto the filter housing top.
Important: HAND TIGHTEN ONLY!
Step 5:
Reconnect the ¼
”
clear drain tube into the fitting on the filter housing bowl. Make sure that it fully seats
in the fitting and is retained snugly.
Step 6:
Repeat Step 1 through Step 5 for each additional filter.
Black Disc
Filter Cartridge
Top of Filter
Housing