ECS Protector Nitrogen Generator PGEN-30 (PGEN-30E) 

June 2018 - Rev 5 

Engineered Corrosion Solutions 

 11336 Lackland Road 

 St. Louis, MO 63146 

 Phone 1-314-432-1377 



www.ecscorrosion.com 

ECS Protector

 

Nitrogen Generator 

 

 

designed for fire sprinkler systems 

Operating Performance

 

† 

 

Capacity based on NFPA

-

13 30

-

minute fill requirement of largest single system

 

Nitrogen Quality

 

N

2

 Purity at Discharge:

 

98% or greater (Maximum of 2.0% oxygen)

 

N

2

 Pressure at Discharge:

 

Min of 15 psig (1 bar)

 

Max of feed air pressure minus 15 psig (1 bar)

 

N

2

 Water Dew Point:

 

Typically less than 

-

70ºF (

-

 57ºC)                              

 

Note: 

 

When  connecting  an  ECS  Protector  Nitrogen  Generator  to  an  existing  dry  pipe/preaction  fire  sprinkler  system,  the       
existing fire sprinkler system(s) must be limited to a maximum leak rate of less than 3 psig within a 24 hour period, per 
system. 

 

The  ECS  Protector  Nitrogen  Generator  facilitates  the 
patented 

fill and purge

” 

breathing process in the fire 

sprinkler  system  when  paired  with  a  venting  device 
installed  on  the  sprinkler  riser  such  as  the  ECS           

Protector  Manual  Vent  (PAV

-

D)  or  the  ECS  Protector 

Dry  SMART  Vent  (PSV

-

D/DE)  for  dry  and  preaction   

systems. 

 

The  ECS  Nitrogen  Generator  unit  that  includes  the 
following components:

 

• 

Steel  enclosure  cabinet  with  membrane  type   
nitrogen  generator  (no  nitrogen  gas  storage)  and 
manual bypass

 

• 

Power supply 

-

 120 VAC/1 phase/60Hz

 

 

(230 VAC/1 phase/50Hz)

 

• 

Single point nitrogen/air discharge –

 

½

” 

NPT

 

• 

Hour Run Meter 

 

• 

Cycle Counter

 

The  ECS  Nitrogen  Generator  includes  the  following  
function Indications:

 

• 

Bypass  Alarm 

-

  Nitrogen  generator  is  in  the        

By

-

Pass

” 

mode (Flashing Indicator)

 

• 

Leak  Monitoring 

-

  Nitrogen  generator  running  

excessively (Audible Signal)

 

The  ECS  Nitrogen  Generator  includes  the  following 
monitoring outputs:

 

• 

System Power (Digital Output)

 

• 

Bypass Mode Alarm (Digital Output)

 

• 

Nitrogen Generation Mode (Digital Output)

 

• 

Nitrogen Supply Line Pressure (Analog Output)

 

• 

Leak Monitoring (Digital Output)

 

The ECS Nitrogen Generator is designed to be used in 
conjunction with the following components as part of 
the  complete  ECS  Dry  Pipe  Nitrogen  Inerting  (DPNI) 
system:

 

• 

Air maintenance  device  with on board adjustable 
regulator  (recommend  Victaulic  Series  757,  Tyco 
Model AMD

-

1 or Reliable Model A

-

2)

 

• 

Riser

-

mounted  ECS  Protector  Manual  Vent      

(PAV

-

D) or ECS Protector Dry SMART Vent (PSV

-

D)

 

The  ECS  Nitrogen  Generator  can  be  used  with  the  
following optional equipment:

 

• 

ECS Protector  SMART  Gas Analyzer  (SGA

-

1) 

-

  one 

per nitrogen generator is recommended

 

• 

ECS  In

-

Line  Corrosion  Detector  (ILD

-

X) 

-

           

monitoring at least one system is recommended

 

Model 

 

Number

 

Min. Supply Air

 

SCFM (L/min)

 

Total System Capacity 

 

Gallons (Liters)

 

Single System Capacity

† @ 

40 psig (2.4 bar)

 

Gallons (Liters)

 

Single System Capacity

† 

 

@ 20 psig (1.4 bar)

 

Gallons (Liters)

 

PGEN

-

30/(30E)

 

14.3 (405)

 

6,500 (24,605)

 

1,150 (4,353)

 

2,300 (8,706)

 

Summary of Contents for PGEN-30

Page 1: ...acement Filters PGEN FKS Annual Maintenance Gas Membrane PGEN MS 20 Year Expected Service Life The ECS Protector Nitrogen Generator is designed for use in maintaining supervisory gas and facilitating...

Page 2: ...storage and manual bypass Power supply 120 VAC 1 phase 60Hz 230 VAC 1 phase 50Hz Single point nitrogen air discharge NPT Hour Run Meter Cycle Counter The ECS Nitrogen Generator includes the following...

Page 3: ...Power Supply The ECS Protector Nitrogen Generator requires a dedicated power supply to prevent interruption from other equipment The incoming power supply line ties into the top of the terminal block...

Page 4: ...ng where used The nitrogen generator cabinet has two 2 system signals and five 5 outputs that can be monitored by the facility s BMS or fire alarm system The nitrogen generator is operating in the byp...

Page 5: ...N 30E is part number PGEN FKS When maintained properly the nitrogen separation membrane will provide up to 20 years of service life Filter Replacement Procedure Preliminary Steps taking the nitrogen g...

Page 6: ...ce the filter housing bowl has been unscrewed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartridge and then pulling down on the cartridge Di...

Page 7: ...TIGHTEN ONLY Step 9 Replace the filter housing bowl by screwing it onto the filter housing top Important HAND TIGHTEN ONLY Step 10 Tighten the petcock valve to the closed position Step 11 The ECS Pro...

Page 8: ...N 10 PGEN 20 PGEN 30 PGEN 40 PGEN 50 PGEN 60 Total System Capacity 675 gal 950 gal 2 000 gal 3 200 gal 6 500 gal 11 000 gal 18 500 gal 22 500 gal Single System Capacity 40 psi 1 215 gal 265 gal 560 ga...

Reviews: