25
Configuration security code
Configuration security code
Configuration security code
Configuration security code
Configuration security code
The display will show:
Note
Note
Note
Note
Note: the middle display shows the current status of the
configuration security code ("0", "1" or "On").
By and push-button, set "S.CnF" parameter as follows:
0
No protection (it is ever possible to modify all
configuration parameters);
1
ever protected (it is never possible to modify a
configuration parameter);
from 2 to 250 security code for configuration parameter
protection.
NOTE
NOTE
NOTE
NOTE
NOTE: the selected value of a security code cannot be
displayed anymore and, coming back on the "S.CnF"
parameter, the display will show "On" when "S.CnF" is
different from 0 or 1, "0" when "S.CnF" is equal to 0,
"1" when "S.CnF" is equal to 1.
When the security code is forgotten, a new value can
be set.
and the "run time hidden" groups are ever protected by
security code.
Run time groups protected by security code
Run time groups protected by security code
Run time groups protected by security code
Run time groups protected by security code
Run time groups protected by security code
The display will show:
By this parameter it is possible to set if the run time group 2 will
be protected or not by the run time security code.
By and push-button, set "Gr2" parameter as follows:
nO
No protection (it is always possible to modify run time
group 2 parameters)
Yes the run time group 1 parameter modification will be
protected by security code.
Push the FUNC push-button; the instrument memorizes the
new setting and goes to the next parameter.
NOTES
NOTES
NOTES
NOTES
NOTES:1)This selection may be carried out only if a run time
security code has been set (from 2 to 250).
2) The above described selection may be repeated for
all groups of the run time mode.
XKP-1-D1.pmd
25/05/2006, 11.28
25