8
B) AUXILIARY INPUT
B) AUXILIARY INPUT
B) AUXILIARY INPUT
B) AUXILIARY INPUT
B) AUXILIARY INPUT
Fig. 8
AUXILIARY INPUT WIRING
NOTES
NOTES
NOTES
NOTES
NOTES:
1) This input is not isolated
not isolated
not isolated
not isolated
not isolated from measuring input. A double or
reinforced insulation between instrument output and power
supply must be assured by the external instrument.
2) Don’t run input wires together with power cables.
3) Pay attention to the line resistance; a high line resistance
may cause measurement errors.
8
9
10
11
DIG. 1
DIG. 2
DIG. 3
Shield
_
+ mA
or
V
6
5
+
_
G
mA
or
V
5
6
4) When shielded cable is used, it should be grounded at one
side only to avoid ground loop currents.
5) The input impedance is equal to:
< 5
Ω
for 20 mA input
> 200 k
Ω
for 5 V input
> 400 k
Ω
for 10 V input
C) LOGIC INPUTS
C) LOGIC INPUTS
C) LOGIC INPUTS
C) LOGIC INPUTS
C) LOGIC INPUTS
Fig. 9.A - LOGIC INPUTS DIG 1, 2, 3 WIRING
XKP-1-D1.pmd
25/05/2006, 11.28
8