Installation
When the installation is completed make sure to set up the keyboard in accordance with the
installation and the intended use; refer to the
Set-up
section.
The 1504M is for indoor use only.
Power connection
Connect the power supply unit to the keyboard PSU connector 1-10 (refer to
figure 1
) and to
the mains socket.
RS-485 connection to Telemetry Receivers and BED-108
Connect the RS-485 cable to socket 1-13 (refer to
figure 1
):
1504M
BDR-55x
BDR-510/4
BDR-511/2/3
BDR-575
ICU
BED-108
SATURN
Pin
Desc.
Terminal
Terminal
Terminal
Pin
Desc.
Pin
Desc. Terminal Pin
Desc.
6
Pos.
PCM IN-
CTRL IN+
CTRL IN+
2
RS485+
1
COM+ ERNA IN+ RX+ RS485+
7
Neg.
PCM IN+
CTRL IN-
CTRL IN-
1
RS485-
2
COM- ERNA IN- RX- RS485-
1, 4, 5 GND
Do NOT connect!
Details on interconnecting various types of telemetry receivers and termination of the RS-485
line can be found on
figure 2
.
Telemetry Receivers Series BDR-51X and BDR-55X and the BED-108 Control Signal Distributor
Unit will terminate the RS-485 properly by themselves when installed in the correct daisy chain
configuration and do not require additional line termination. The ICU, SATURN and the
BDR-575 are bus-connected and consequently the line must be terminated, on the ICU with an
external resistor, on the BDR-575 by enabling the RS-485 LK1 jumper on the interface board,
and on the SATURN by setting a link across J9.
For more details, please refer to the documentation for the specific Telemetry Receiver.
Different types of telemetry receivers can also be mixed on the common control line.
Remember, that each telemetry receiver must have an unique address, refer to the relevant
telemetry receiver manual.
Maximum cable length is 1200 metres. However, telemetry receivers Series BDR-51X and
BDR-55X as well as the BED-108 features an active control signal repeater allowing further
3000 meters (BDR-51X further 1200 meters) distance to the next unit.
RS-232-C connection to E-Mux Multiplexer
Connect the RS-232-C cable to socket 1-13 (refer to
figure 1
).
1504M
E-Mux Multiplexer
Pin
Description
Pin
Description
3
Transmit
2
Receive
2
Receive
3
Transmit
1, 4 or 5 Ground (To cable screen also)
5
Ground (To cable screen also)
Maximum cable length is 15 meters.
Only
one
E-Mux can be connected to the 1504M.
1504M E-Mux & PTZ control
2821-00062
Page 3