Param.
Description
Setting range
Default
value
2-13
Alarm output 3, high or low
0 ->
Contact closed by low limit
1 ->
Contact closed by high limit
2 ->
Contact open by low limit
3 ->
Contact open by high limit
0 .. 3
0
2-14
Alarm output 3, alarm point
-99999 .. 999999
0
2-15
Alarm output 3, hysteresis
1 .. 1000
1
2-16
Alarm output 3, release delay time
in seconds
0 .. 60
0
2-17
Alarm output 3, operate delay time
in seconds
0 .. 60
0
2-18
Alarm output 4, data source
0 ->
Alarm 4, off
1 ->
Alarm 4 to value of encoder
2 ->
Alarm 4 to maximum value
3 ->
Alarm 4 to minimum value
4 ->
Alarm 4 to hold value
0 .. 4
0
2-19
Alarm output 4, high or low
0 ->
Contact closed by low limit
1 ->
Contact closed by high limit
2 ->
Contact open by low limit
3 ->
Contact open by high limit
0 .. 3
0
2-20
Alarm output 4, alarm point
-99999 .. 999999
0
2-21
Alarm output 4, hysteresis
1 .. 1000
1
2-22
Alarm output 4, release delay time
in seconds
0 .. 60
0
2-23
Alarm output 4, operate delay time
in seconds
0 .. 60
0
2End
Leave programming level P-02
22
ERMA-Electronic GmbH
8. Procedure of programming