Instruction manual for installation and operation of automatic pellet burner “ERATO GP20+”
(Version :
02.02.2010 10:36
)
p.
42/50
•
In case that this quantity is
higher than required, than
decrease the thermal
capacity of the unit or
increase the air flow rate
by repositioning the
control flap of the air fan;
15.
High
temperature of
the flue gases (if
flue gas
thermometer is
mounted)
The heat exchanging
surfaces of the heat
consumer are
deposited with ash,
presenting heat
resistive layer, thus
decreasing the heat
exchanging intensity
It is necessary to clean thoroughly
the heat consumer surfaces in
order to decrease ash layer heat
resistance;
16.
Flue gases are
emitted out of
the heat
consumer unit
after certain
period of
exploitation
The flue gas duct is
clogged or even
blocked by fly ash
deposits
It is necessary to clean thoroughly
the heat consumer’s flue gas duct
as well as chimney
;
17.
Other failures,
not described
above
It is necessary to consult
authorized technician and
eventually service maintenance
should be performed
Table 5.3.
Automatic pellet burner faults and repair procedures
.