Terminal
Function
1 .2
Power supply (phase conductor)
1 .6
Power supply (neutral conductor)
1 .1, 1 .5
Phase conductor connection, channel 1
2 .1, 2 .5
Switched phase channel 1
3 .1, 3 .5
Phase conductor connection, channel 2
4 .1, 4 .5
Switched phase channel 2
1 .4, 1 .8
Phase conductor connection, channel 3
2 .4, 2 .8
Switched phase channel 3
3 .4, 3 .8
Phase conductor connection, channel 4
4 .4, 4 .8
Switched phase channel 4
The switching channels have potential-free relay con-
tacts .
The total connected load of all channels must
not exceed 25 A .
Permitted cable cross sections for connecting to the
actuator:
Rigid cable
[mm
2
]
Flexible cable with ferrule [mm
2
]
0 .14 – 2 .50
0 .14 – 1 .50
7 Start-up
7.1 Simple operator functions using inte-
grated buttons
The device features one control button per channel .
You can operate the actuator by means of these but-
tons immediately (no teaching-in required) and check
that the electrical installation has been performed
correctly .
Simply press and release the button to operate
the actuator . Pressing and holding down the
button (for more than 4 seconds) will switch the
relevant channel of the actuator to teach-in
mode .
The relevant channel LED signals the switching status
of the relay:
•
LED on - relay contact enabled
•
LED off - relay contact disabled