EPS-32-V1 / EPS-32-V2 / EPS-16  Installation Manual                                                                                                                               Revision 7.0  05102020 

SECTION 1:  Introduction 

 

Edge Power Solutions rack mount power distribution units have been designed to p56VDC at up to 98W per output 

(See 

Note 1)

 to low voltage DC devices such as: 

 

 

GPON Optical Network Terminals 

 

Distributed Antenna Systems  

 

LED Lighting 

 

CCTV 

 

Wireless Access Point 

 

Other applicable devices with similar input needs.  

 

 

  NOTE 1:    

 

1.

 

EPS-16 

a.

 

The maximum output per port is 98W 

b.

 

The maximum combined output for 120VAC input/or RMS Equivalent = 1400W 

c.

 

The maximum combined output for 208-240VAC input/or RMS Equivalent = 1600W 

 

2.

 

EPS-32-V1 (DUAL 15A INPUT) 

a.

 

The maximum output per individual port is 98W 

b.

 

The maximum combined output for 120VAC input/or RMS Equivalent = 2800W (1400W INPUT 1 + 1400W INPUT 2) 

c.

 

The maximum combined output for 208-240VAC input/or RMS Equivalent= 3200W (1600W INPUT 1 + 1600W 

INPUT 2) 

 

3.

 

EPS-32-V2 (SINGLE 20A INPUT) 

a.

 

The maximum output per individual port is 98W 

b.

 

The maximum combined output for 120VAC input/ or RMS Equivalent = 1960W 

c.

 

The maximum combined output for 208-240VAC input/ or RMS Equivalent = 2800W Outputs  

 

For Product Assistance or Technical Support call:  321-499-1919 - Option 4 

 

1.1

 

Quick Installation Checklist 

 

 

The following steps are recommended to quickly install the EPS-RM-1x(xx)-100W-(s) Power Supply Unit for use.  

a)

 

Attach Rack Mount Brackets to the Power Supply Unit (Rack mount unit)  

b)

 

Mount the power supply unit in rack or wall location 

c)

 

Connect Safety Earth Ground connection to approved ground buss 

d)

 

Connect devices to output connections using properly sized wire.  (12AWG-24AWG) 

e)

 

Connect to properly sized AC power source(s)  

 

 

 

PAGE 1 

 

Summary of Contents for EPS-16

Page 1: ...EDGE POWER SOLUTIONS 56VDC SERIES USER MANUAL VERSION 7 05 2020 USER MANUAL EPS 16 EPS 32 V1 EPS 32 V2 ...

Page 2: ...changes are made periodically These changes are incorporated in newer publication editions Edge Power Solutions may improve and or change products described in this publication at any time Due to continuing system improvements Edge Power Solutions is not responsible for inaccurate information which may appear in this manual For the latest updates consult the Edge Power Solutions website at www edg...

Page 3: ...ndard Accessories Additional Required Items Safety Precautions Mounting PDU Attaching Safety Earth Ground Connection Installing Phoenix Connectors Connecting Output to Field Devices Connecting to AC power Source Connection to DC power source Rack Mount Connection to DC power source Wall Mount SECTION 3 Optional Integrated Fiber Optic Splitter Safety Precautions Source Signal Connection s Output Co...

Page 4: ...or 120VAC input or RMS Equivalent 2800W 1400W INPUT 1 1400W INPUT 2 c The maximum combined output for 208 240VAC input or RMS Equivalent 3200W 1600W INPUT 1 1600W INPUT 2 3 EPS 32 V2 SINGLE 20A INPUT a The maximum output per individual port is 98W b The maximum combined output for 120VAC input or RMS Equivalent 1960W c The maximum combined output for 208 240VAC input or RMS Equivalent 2800W Output...

Page 5: ...Fiber Optic Splitter EPS 16 1RU 1 75 H x 16 D x 17 W 16 6 LBS 1 15A C19 Inputs 16 56VDC Outputs 12AWG 24AWG Up to 98W per output a SEE NOTE 1 PAGE 1 16 Resettable 1 75A Breaker 1 per output Optional 1x16 Passive Fiber Optic Splitter EPS 16 Wall Mount 24 W x 24 L x 6 25 23lbs 1 15A C19 Inputs Option High Voltage DC Input 16 56VDC Outputs 12AWG 24AWG Up to 98W per output a SEE NOTE 1 PAGE 1 16 Reset...

Page 6: ... 2 Rack Mounting Ears EPS 32 V2 1 6 C20 5 20P Power Cord AC Version 4 16 Position Phoenix Connectors Optional 2 Position Connectors Available 1 Grounding Lug Kit 2 Rack Mounting Ears EPS 16 1 6 C20 5 15P Power Cord AV Version 2 16 Position Phoenix Connectors 1 Grounding Lug Kit Optional 2 Position Connectors Available 2 Rack Mounting Ears 2 2 Additional Required Items Small Tip Flat Head Screwdriv...

Page 7: ...his equipment should only be installed by qualified personnel Always disconnect the power supply cord s before servicing to avoid electrical shock For products with 2 input power cords both must be disconnected before servicing Do not block venting holes when installing this product Allow for maximum airflow at all times above below and each side of the unit WARNING Earth Ground connection is esse...

Page 8: ...is o Units should be mounted in a manner that allows for proper air intake and venting Do not block the side or top vent openings When mounting in an enclosure or cabinet the enclosure or cabinet should have a means of ventilation in the form of side vents open or perforated doors and or mechanical ventilation methods Allow at minimum 3 of clearance on each side of the unit and 1 75 1RU of clearan...

Page 9: ...ctor removal is required use care to avoid bending the pins of the receiving connector 2 6 2 Insert Optional 2 port Phoenix Connectors Insert optional 2 position male Phoenix connector into matching 16 position female Phoenix interface on front face of the chassis Observe proper polarity when terminating connector o With the screw at the top the negative terminal is on the left the positive termin...

Page 10: ...nufacturer for device requirements o Recommended strip length Tighten screw above input until cable is secure 2 8 Connecting AC Power SEE NOTE 1 PAGE 1 Connected provided cord to AC input on rear of chassis o Units can accept up to 240VAC with appropriate cable Push adjacent power switch es to the On Reset Position when ready to power on unit and connected devices o Turn on CB1 EPS 16 EPS 32 V2 o ...

Page 11: ...DC power source is powered off and discharged Utilizing provided locking cord kit connect the open lead end of cable to DC power source equipment o White Lead to Negative o Black Lead to Positive o Green Lead to GND Ground Plug locking cables into the chassis inputs NOTE Do NOT disconnect locking plugs until source power has been powered off and discharged PAGE 8 ...

Page 12: ...igital Electricity receiver connection Connection Point 2 in illustration below EPS wall mount PDUs have internal shelves for Digital Electricity receiver mounting Follow Volt Server connection procedures Volt Server connection procedures take precedence over EPS instructions DC Power out from receiver to PDU power supply connections o Negative Lead to Power Supply Neutral Input o Positive Lead to...

Page 13: ...nel position 3 1 2 Output Connection Connect output from positions 1 32 on EPS RM 1x32 100W s or positions 1 16 on EPS RM 1x16 100W S Patch other end to servicing device or device servicing fiber patch panel position On 16 Port Unit Utilize included 1x2 splitter for 2x16 connection END PAGE 10 WARNING Avoid eye exposure to fiber optic openings on this device when connected to external equipment in...

Reviews: