background image

E-mail: [email protected]

Made in Rome, New York, USA

20

COMMON TO ALL AIR HANDLERS - SEQUENCE OF OPERATION

 

Continued

OPTIONAL HEATPUMP WITH 

ELECTRIC HEAT 

(2-Stage Heating)

 

Important:

 The dip switch 1=OFF/Open

The dip switch 2=ON/2

 

For heat pump operation with backup electric heat, first 

turn the unit on via the 

On/off

 button. Select 

Heat

 mode via 

the 

Mode

 button. The room temperature will be displayed. 

Then, by depressing either the 

Up

 or 

Down

 arrow once, the 

setpoint temperature will appear. The setpoint temperature 

can then be changed with each successive press of the 

Up

 

or 

Down

 arrow or by holding the button in.

 

Place the setpoint temperature one-degree above the 

room temperature. The compressor will start and heating 

will continue for a minimum of two minutes and as long as 

the setpoint remains above room temperature. Once the 

room temperature is satisfied and the two-minute minimum 

run time has elapsed, the compressor will cycle off. 
 

(*) 

On initial startup (or if power is lost) there is a three-

minute delay between compressor re-starts.

 

(**) 

Some EMI Heat pump condensers are equipped 

with a low temperature cutout that will shut down the con-

denser and energize the indoor heat. This is designed to 

protect the compressor under certain outdoor conditions. 

 

(***) 

Some EMI Heat pump condensers energize the 

indoor unit electric heat during defrost.

 

Next,  place  the  setpoint  temperature  at  least  two 

degrees  above  room  temperature. The  electric  heat  will 

energize along with the compressor (heatpump) thus two-

stage heating. The electric heat will continue to run until the 

deviation between room temperature and setpoint tempera-

ture is less than two degrees. At that time the electric heat 

will switch off and the heatpump will take over the heating 

demand. Once the room temperature is satisfied and the 

two-minute minimum run time has elapsed, the compressor 

will cycle off. There is then a three-minute delay before the 

compressor can restart. The fan will operate as described 

in “Fan Operation”

 

(

Figure 5)

.

DRY MODE OPERATION

 

Dry  mode  will  remove  humidity  from  the  air  while 

maintaining a specific setpoint temperature. This is done 

by energizing the compressor in cooling along with the elec-

tric or hydronic heater. Dry mode 

will not

 maintain a specific 

humidity level. The unit must be equipped with an optional 

electric heat element or hydronic coil.

 

For Dry Mode operation first turn the unit on via the 

On/

off

  button. Select 

Dry 

mode via the 

Mode

 button. The room 

temperature will be displayed. Then by depressing either the 

Up

 or 

Down

 arrow once, the setpoint temperature will appear. 

The setpoint temperature can then be changed with each 

successive press of the 

Up

 or 

Down

 arrow or by holding the 

button in.

 

Place the setpoint temperature at a desired room tempera-

ture. Depending on the difference between room temperature 

and set point temperature the compressor and/or heat source 

will energize. If the room temperature and setpoint temperature 

are the same the compressor will operate in cooling and the 

electric heat source will also energize.

 

Should the room temperature fall below the setpoint 

temperature by two degrees, the compressor will stop and 

heating will continue to boost the room temperature back up 

to stepoint temperature. If the room temperature rises above 

the setpoint temperature by two degrees, heating will stop and 

cooling will continue to bring the room temperature back down 

to stepoint temperature. The fan will operate continuously at 

low speed while in Dry Mode.

 

In order to prevent short cycling the minimum on time for 

both cooling and heating is two minutes. The minimum off 

time is 3 minutes

 

(

Figure 5)

.

OPTIONAL ELECTRIC HEAT OPERATION

 

(Non Heat Pump Condenser Units Only)

Important:

 The dip switch 1& 2 must be set to ON

 

For electric heat operation first turn the unit on via the 

On/Off

  button. Select 

Heat 

mode via the 

Mode

 button. The 

room temperature will be displayed. Then by depressing 

either the 

Up

 or 

Down

 arrow once, the setpoint temperature 

will appear. The setpoint temperature can then be changed 

with each successive press of the 

Up

 or 

Down

 arrow or 

by holding the button in. Place the setpoint temperature 

above room temperature. The electric heat will energize 

and heating will continue as long as the setpoint remains 

above room temperature. Once the room temperature is 

satisfied the electric heat will cycle off. The fan will operate 

as described in “Fan Operation”

 

(

Figure 5)

.

UNITS WITH CONDENSATE PUMPS

   EMI Air Handlers are available with an optional con-

densate  pump.  Condensate  pumps  are  recommended 

when it is not possible to gravity drain the condensation 

from the indoor unit. Depending on the pump manufacture 

the maximum lift for the pump will vary. Consult the pump 

instructions  for  the  maximum  lift  for  the  particular  pump 

being used or refer to specific pump kit information and 

instructions as supplied by EMI. 

   Condensation  generated  by  the  evaporator  will  col-

lect in the pumps’ reservoir. When the water level is high 

enough, a float switch will close and energize the pump 

motor  clearing  the  water  from  the  reservoir.  Should  for 

any reason the water exceed the maximum preset level, 

a safety switch will open, there by interrupting the (Y) sig-

nal to the condenser. This will prevent the evaporator from 

generating more condensation and spilling out of the unit.

  

Summary of Contents for CHP

Page 1: ...NCE MANUAL EMI DUCTLESS SPLIT SYSTEM AIR HANDLERS FLOOR MODEL AIR HANDLER FCP FHP WALL MOUNTED AIR HANDLER WCP WHP CEILING MOUNTED AIR HANDLER CHP An ISO 9001 2000 Certi ed Company Enviromaster Intern...

Page 2: ...lting in re electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual to be su...

Page 3: ...ring 18 awg required High voltage power supply wiring Mounting fasteners screws wall anchors etc Chilled water condensate and refrigerant piping Refrigerant for interconnect charge Hot water piping Fl...

Page 4: ...unit The cabinet service panels must be able to be removed without obstruction FCP FHP CCP CHP units can be equipped with hot water coil Unit mount control panel standard on FHP FCP and WHP WCP optio...

Page 5: ...l surfaces LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS In addition to the Y and C connections required for cooling heat pumps require a reversing valve control wire O orange that is energiz...

Page 6: ...Heat pump operation requires the connection of the O orange terminal from the outdoor unit to the thermostat The reversing valve is energized in the cooling mode for EMI models SHC heat pump condenser...

Page 7: ...according to the table below Figure 4 FHP FCP to gain access to the relay board rst remove the return air grill from the bottom front of the unit The relay board is located in the control section Set...

Page 8: ...for mounting the unit for optimum air circulation 3 Locate the indoor and outdoor units as close together as possible See outdoor unit requirements UNIT MOUNTING The FHP FCP is designed to sit direct...

Page 9: ...FRIGERANT PIPING The FHP is equipped with a Flo Rater Piston Expan sion Device Connections are male are type are nuts not included The suction line large must be insulated the entire length with close...

Page 10: ...DIMENSIONS AND SPECIFICATIONS NOTE Due to ongoing development programs design and speci cations may change without notice FCP PIPING SPECIFICATIONS Model Chilled Water Line Size Supply Return Drain H...

Page 11: ...om FHP Electric Heat Speci cations table 36 requires piston kit 550 121 see pg 5 FCP FHP ELECTRICAL HEAT SPECIFICATIONS Model Voltage KW Heater Amps Total Amps Min Circuit Amps Max Fuse Amps 9 12 15 2...

Page 12: ...torized Damper and Power Assisted Fresh Air 2 Fan Type Wall Box Dimensions 14 from nished oor level x 17 wide x 8 deep Model Air Handler Condenser Btuh Factory Installed Field Changeover Part Piston O...

Page 13: ...Use the cardboard template provided with unit packing to test t the unit before installation 1 The CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Using...

Page 14: ...3 4 Flare nuts not included CHP WITH ELECTRIC HEAT OPTIONS Model Voltage KW Htr Amps Total Amps Min Cir Amps Max Fuse 12 208 230 3 13 1 13 7 17 1 20 18 24 208 230 5 21 7 22 8 28 6 30 CHP ELECTRICAL SP...

Page 15: ...rom unit Determine if the cabinet front can be removed with out obstruction WALL MOUNTED AIR HANDLER WCP WHP NOTE Please refer to the Common section in the front of this manual for more detailes on Co...

Page 16: ...Factory Installed Field Replacement Part Piston Ori ce Piston Ori ce Size Part Piston Ori ce Piston Ori ce Size WHP12 9 000 240 4064 044 240 727 041 12 000 NO CHANGE WHP18 15 000 240 4111 053 240 101...

Page 17: ...21 7 22 3 27 9 30 36 230 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45...

Page 18: ...is designed to optimize system performance and protect the refrigeration system from unwanted short cycling and evaporator freeze ups Operation of the unit can be made by either the keypad on the uni...

Page 19: ...ton Select Cool mode via the Mode button The room temperature will be displayed Then by depressing either the Up or Down arrow once the setpoint temperature will appear The setpoint temperature can th...

Page 20: ...tpoint temperature will appear The setpoint temperature can then be changed with each successive press of the Up or Down arrow or by holding the button in Placethesetpointtemperatureatadesiredroomtemp...

Page 21: ...quipped with an auto on fan switch When this switch is placed in the on position the indoor fan will run continuous When the switch is in the auto position the indoor fan will cycle with the call for...

Page 22: ...system or from abnormally cold air from the evaporator coil Should the freeze sensor activate the indoor fan will switch off to eliminate the source of cold fresh air and also the outdoor condensing...

Page 23: ...l Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering A...

Page 24: ...ailure to do so could result in physical injury and or electrical shock When trouble shooting the indoor unit please refer to the wiring diagram that is supplied with the equipment It is located eithe...

Page 25: ...mote thermostat connection A 24V transformer located in the indoor air handler unit as of 12 01 04 provides low Volt control power to both the indoor air handler and outdoor condenser The 24V power su...

Page 26: ...eversing valve will not be energized To check for a condenser signal place the indoor unit or wall thermostat in heating Next place the set point temperature one degree above room temperature to call...

Page 27: ...ce all circuit boards including the unit keypad Do not attempt to trouble shoot the individual circuit boards Q The display tends to icker at times Is this normal A A small amount of ickering of the d...

Page 28: ...or application by others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs nee...

Reviews: