www.enviromaster.com
The Ductless Split System of Choice
11
NOTE:
Due to EMI’s ongoing development programs, designs and specifications may change without notice.
(FCP/FHP) DIMENSIONS AND SPECIFICATIONS
Continued
26”
10
1
/
2
”
47” (09-30), 61
1
/
2
” (36-48)
FHP’s ONLY
Hydronic Coil
Location
Hydronic Coil
Evaporator Coil
FCP/FHP FRESH AIR SPECIFICATIONS*
Model #
Total CFM
Outside Air CFM
9/12, 15
440
50
18/24, 30
725
75
36/42, 48
1200
160
* Open or Motorized Damper
FCP/FHP ELECTRICAL SPECIFICATIONS
Model #
Voltage/Hz/Ph
Fan
FLA
Min.
Ampacity*
Max.
Fuse*
9/12A
115/60/1
1.5
1.9
15
9/12, 15
208-230/60/1
0.6
0.8
15
18/24
208-230/60/1
0.8
1
15
30
208-230/60/1
1.1
1.4
15
**36/42, 48
208-230/60/1
1.1/1.1
2.5
15
* If electric heat is installed, use data from
FHP Electric Heat Specifications
table.
** 36 requires piston kit #550-121 (see pg 5)
FCP/FHP ELECTRICAL HEAT SPECIFICATIONS
Model#
Voltage
KW
Heater
Amps
Total
Amps
Min.
Circuit
Amps
Max.
Fuse
Amps
9/12, 15
230
3
13.1
13.7
17.1
20
18/24
230
5
21.7
22.7
28.2
30
30
230
5
21.7
22.8
28.6
30
36/42, 48
230
7
30.4
32.6
40.6
45
FHP PIPING SPECIFICATIONS
Model#
Refrigerant Line Size
Drain Hose
Liquid
Suction
Flare*
Flare*
9/12
1/4”
1/2”
1/2” I.D.
15
1/4”
5/8”
1/2” I.D.
18
3/8”
5/8”
5/8” I.D.
24
3/8”
3/4”
5/8” I.D.
30
3/8”
3/4”
5/8” I.D.
36/42, 48
3/8”
3/4”
5/8” I.D.
* Flare fittings NOTE: Flare nuts not included.
FCP/FHP HYDRONIC HEAT SPECIFICATIONS
(Single-stage Heating only)
Model#
EWT °F
Btuh
GPM
PD Ft. H
2
O
9/12, 15
180
24,300
2.0
3.4
140
18,400
2.0
3.4
18/24, 30
180
41,500
3.5
5.6
140
26,200
3.5
5.6
36/42, 48
180
39,500
6.0
8.8
140
62,400
6.0
8.8
NOTE: Not available with Heat Pump applications.
FHP SHIPPING WT.
Model#
LBS.
9/12, 15
110
18/24, 30
120
36/42, 48
165