Enviromaster CHP Nstallation, Operation And Maintenance Manual Download Page 19

www.enviromaster.com

The Ductless Split System of Choice

19

COMMON TO ALL AIR HANDLERS - SEQUENCE OF OPERATION

 

Continued  

ON/OFF SWITCH

 

The 

On/Off

 switch is used to turn the equipment on or 

off. In the 

off

 mode the display will be blank and all LED 

indicator lights will be dark. To turn on the unit press the 

On/off

 button once. Room temperature will be displayed 

and amber LED indicators will show fan speed and mode 

selections (

Figure 5)

.

FAN OPERATION

 

The indoor unit utilizes a two-speed motor with three 

operational fan modes. The 

Fan

 button will allow the selec-

tion of the desired fan setting. An amber LED indicator will 

light next to the fan speed selection. If 

Auto

 fan mode is 

selected then an LED indicator will also light next to 

Auto.

 

High

 and 

Low

 are constant fan settings. The fan will 

operate continuous regardless of set point or room tem-

peratures. 

Auto

 mode is a cycling fan setting.

 

Auto

 fan mode can only be selected if the unit is in 

Heat

 or 

Cool 

mode. In 

Auto

 mode the fan will cycle with 

the call for Heat or Cool. Fan speed will be determined by 

the microprocessor and speed adjustment will be made 

according to room and setpoint temperatures. The fan will 

switch to 

High

 speed when room temperature deviates by 

MODE SWITCH

 

(System Switch)

 

The 

Mode

 button will allow the selection of the desired 

mode of operation. Colored LED indicators will light next 

to the selected mode. With each successive press of the 

Mode

 button, selection will rotate between 

Heat, Cool, 

Fan or Dry 

mode. If the dipswitches are set for cooling 

only (off – off) then 

Heat

 and 

Dry

 will not be accessible 

(

Figure 5)

.

COOLING ONLY OPERATION

 

For cooling operation first turn the unit on via the 

On/off

 

button. Select 

Cool

 mode via the 

Mode

 button. The room 

temperature will be displayed. Then, by depressing either 

the 

Up

 or 

Down

 arrow once, the setpoint temperature will 

appear. The setpoint temperature can then be changed with 

each successive press of the 

Up

 or 

Down

 arrow buttons 

or by holding the button in. Place the setpoint temperature 

below the room temperature. The compressor will start and 

cooling will continue for a minimum of two minutes and as 

long as the setpoint remains below room temperature.

 (On 

initial startup or if power is lost, there is a three-minute delay 

between compressor re-starts.)

 

 

Once the room temperature is satisfied and the two-

minute minimum run time has elapsed the compressor will 

cycle off. The fan will operate as described in “Fan Opera-

tion”

 

(

Figure 5)

.

NOTE:

 

Once the compressor is switched off there 

is a three-minute delay before it will re-start.

more than two degrees from setpoint. The fan will switch 

to low speed if the deviation is one degree. When the room 

temperature reaches setpoint temperature the heat/cool call 

will then be dropped. The fan will stay on for an additional 

60 sec. to purge unit of any residual energy. After the fan 

has been off for ten minutes, the fan will cycle on for 60 

seconds. This is done so the microprocessor can sample 

the room air and also helps eliminate room temperature 

stratification. 

 

When the unit is in 

Dry

 mode the fan speed will remain 

constant at 

low

 speed. While the unit is in 

Fan

 mode, 

Auto

 

is bypassed and only 

High

 or 

Low

 are available (

Figure 5)

.

 

START-UP FOR UNIT MOUNTED INFRARED COMPATIBLE CONTROL 

(Only)

UNIT MOUNTED INFRARED COMPATIBLE CONTROL

Figure 5

1

2

3

4

5

6

7

8

9

1. LCD Display

2. Temp. Set Point Down Button
3. Temp. Set Point Up Button

4. Infrared Sensor

5. Power ON/OFF Button

6. Mode Indicator LEDs (HEAT, COOL, FAN, DRY)

7. Mode Selection Button

8. Fan Operation Button

9. Fan Indicator LEDs (HIGH, LOW, AUTO)

Summary of Contents for CHP

Page 1: ...NCE MANUAL EMI DUCTLESS SPLIT SYSTEM AIR HANDLERS FLOOR MODEL AIR HANDLER FCP FHP WALL MOUNTED AIR HANDLER WCP WHP CEILING MOUNTED AIR HANDLER CHP An ISO 9001 2000 Certi ed Company Enviromaster Intern...

Page 2: ...lting in re electrical shock property damage personal injury or death TO THE INSTALLER 1 Retain this manual and warranty for future refer ence 2 Before leaving the premises review this manual to be su...

Page 3: ...ring 18 awg required High voltage power supply wiring Mounting fasteners screws wall anchors etc Chilled water condensate and refrigerant piping Refrigerant for interconnect charge Hot water piping Fl...

Page 4: ...unit The cabinet service panels must be able to be removed without obstruction FCP FHP CCP CHP units can be equipped with hot water coil Unit mount control panel standard on FHP FCP and WHP WCP optio...

Page 5: ...l surfaces LOW VOLT INTERCONNECT WIRING FOR UNIT MOUNTED CONTROLS In addition to the Y and C connections required for cooling heat pumps require a reversing valve control wire O orange that is energiz...

Page 6: ...Heat pump operation requires the connection of the O orange terminal from the outdoor unit to the thermostat The reversing valve is energized in the cooling mode for EMI models SHC heat pump condenser...

Page 7: ...according to the table below Figure 4 FHP FCP to gain access to the relay board rst remove the return air grill from the bottom front of the unit The relay board is located in the control section Set...

Page 8: ...for mounting the unit for optimum air circulation 3 Locate the indoor and outdoor units as close together as possible See outdoor unit requirements UNIT MOUNTING The FHP FCP is designed to sit direct...

Page 9: ...FRIGERANT PIPING The FHP is equipped with a Flo Rater Piston Expan sion Device Connections are male are type are nuts not included The suction line large must be insulated the entire length with close...

Page 10: ...DIMENSIONS AND SPECIFICATIONS NOTE Due to ongoing development programs design and speci cations may change without notice FCP PIPING SPECIFICATIONS Model Chilled Water Line Size Supply Return Drain H...

Page 11: ...om FHP Electric Heat Speci cations table 36 requires piston kit 550 121 see pg 5 FCP FHP ELECTRICAL HEAT SPECIFICATIONS Model Voltage KW Heater Amps Total Amps Min Circuit Amps Max Fuse Amps 9 12 15 2...

Page 12: ...torized Damper and Power Assisted Fresh Air 2 Fan Type Wall Box Dimensions 14 from nished oor level x 17 wide x 8 deep Model Air Handler Condenser Btuh Factory Installed Field Changeover Part Piston O...

Page 13: ...Use the cardboard template provided with unit packing to test t the unit before installation 1 The CHP Series is designed to be mounted to a horizontal surface which should be plumb and level 2 Using...

Page 14: ...3 4 Flare nuts not included CHP WITH ELECTRIC HEAT OPTIONS Model Voltage KW Htr Amps Total Amps Min Cir Amps Max Fuse 12 208 230 3 13 1 13 7 17 1 20 18 24 208 230 5 21 7 22 8 28 6 30 CHP ELECTRICAL SP...

Page 15: ...rom unit Determine if the cabinet front can be removed with out obstruction WALL MOUNTED AIR HANDLER WCP WHP NOTE Please refer to the Common section in the front of this manual for more detailes on Co...

Page 16: ...Factory Installed Field Replacement Part Piston Ori ce Piston Ori ce Size Part Piston Ori ce Piston Ori ce Size WHP12 9 000 240 4064 044 240 727 041 12 000 NO CHANGE WHP18 15 000 240 4111 053 240 101...

Page 17: ...21 7 22 3 27 9 30 36 230 5 21 7 22 3 27 9 30 WCP CAPACITIES Model Nominal Capacaties Total Capacity Sensible Capacity Fluid Temp Fluid Flow PD Ft H2 0 09 12 9 000 7 375 6 732 45 1 0 8 10 801 8 272 45...

Page 18: ...is designed to optimize system performance and protect the refrigeration system from unwanted short cycling and evaporator freeze ups Operation of the unit can be made by either the keypad on the uni...

Page 19: ...ton Select Cool mode via the Mode button The room temperature will be displayed Then by depressing either the Up or Down arrow once the setpoint temperature will appear The setpoint temperature can th...

Page 20: ...tpoint temperature will appear The setpoint temperature can then be changed with each successive press of the Up or Down arrow or by holding the button in Placethesetpointtemperatureatadesiredroomtemp...

Page 21: ...quipped with an auto on fan switch When this switch is placed in the on position the indoor fan will run continuous When the switch is in the auto position the indoor fan will cycle with the call for...

Page 22: ...system or from abnormally cold air from the evaporator coil Should the freeze sensor activate the indoor fan will switch off to eliminate the source of cold fresh air and also the outdoor condensing...

Page 23: ...l Number Technician Serial Number Mode Cooling Indoor Section Notes Evaporator Entering Air DB Evaporator Entering Air WB Evaporator Leaving Air DB Evaporator Leaving Air WB Outdoor Section Entering A...

Page 24: ...ailure to do so could result in physical injury and or electrical shock When trouble shooting the indoor unit please refer to the wiring diagram that is supplied with the equipment It is located eithe...

Page 25: ...mote thermostat connection A 24V transformer located in the indoor air handler unit as of 12 01 04 provides low Volt control power to both the indoor air handler and outdoor condenser The 24V power su...

Page 26: ...eversing valve will not be energized To check for a condenser signal place the indoor unit or wall thermostat in heating Next place the set point temperature one degree above room temperature to call...

Page 27: ...ce all circuit boards including the unit keypad Do not attempt to trouble shoot the individual circuit boards Q The display tends to icker at times Is this normal A A small amount of ickering of the d...

Page 28: ...or application by others Failure to start due to voltage conditions blown fuses open circuit breakers or other damages due to the inadequacy or interruption of electrical service Damage or repairs nee...

Reviews: