Initial Installation
QUALIFIED INSTALLERS ONLY
v
enting
c
LeaRances
:
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a
horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 1½” (38 mm) on the
sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance
are necessary.
Table 2. Vent Pipe Minimum Clearances.
Vertical Pipe to
the Side Walls
Horizontal Pipe to
the Sides & Bottom
Above an Elbow
Above the Unit
Above an Elbow
Not Above the Unit
Above Horizontal
Vent Pipe
Wall Frame 8”
(203mm) or less
Hard
Pipe
1”
(25.4 mm)
1½”
(38.1 mm)
3”
(76.2 mm)
3”
(76.2 mm)
2”
(51 mm)
10”x10”
(25x25cm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 27) will assure the proper support and spacing for
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for
passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
The configuration of the venting pipes depends on the locations
of walls, ceilings, and studs. However, the pipes cannot be of
arbitrary length and arrangement. Because the length of the
vertical and horizontal sections dramatically affects the burning
efficiency of the fireplace, certain guidelines have been set
in
I
nItIal
I
nstallatIon
- a
llowaBle
V
ent
c
onfIguratIons
.
Venting
terminals can not be recessed into a wall or siding.
WARNING: This gas appliance must not be connected
to a chimney flue serving a separate solid-burning
appliances.
Figure 27. Vent Framing For Wall or Ceiling.
D
iRect
v
ent
:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the bottom of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the S20I/ S20ID must be between 7” (18 cm) and 44ft (13.4 m). This model is vented
with co-axial 4” intake, 6 5/8” exhaust aluminum or stainless steel approved rigid vent leading into a vertical
or horizontal termination cap. The flue collar of this model will fit inside of a standard 4” x 6 5/8” vent and
must be either correctly interlocked or fastened, with three screws directly to the vent.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been properly
sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must be installed
in the correct location on top or rear of the S20I/ S20ID.
22
a
ppRoveD
v
enting
p
aRts
:
Table 3: Approved Vent Manufacturers
Manufacturer
Brand Name
Nominal Sizes
ICC
EXCELDirect
4” x 6 5/8”
M&G Dura-Vent
Direct Vent Pro
4” x 6 5/8”
Selkirk
DIRECT-TEMP
4” x 6 5/8”
Selkirk
AMP DV
4” x 6 5/8”
Metal-Fab Inc.
Sure-Seal
4” x 6 1/2”
This fireplace has been tested and certified
for use with the venting brand names listed
in table 3. Refer to table 4 for part numbers
of commonly used parts for both venting
systems. For more venting parts please visit
the respective manufacturers’ website.
WARNING: Do not mix parts from
different vent manufacturers’ systems.