Initial Installation
QUALIFIED INSTALLERS ONLY
g
as
L
ine
c
onnection
:
WARNING: Only persons licensed to work with gas piping
may make the necessary gas connections to this
appliance.
Gas Line Connection:
• A ⅜” 45° flared fitting and flex connector are supplied with
the unit (see Figures 35 and 36). Consult the local authorities
for local codes or use the CAN/CGA B149 (1 or 2) installation
code in Canada. In the US, gas installations follow either local
codes or the current edition of the National Fuel Gas Code
ANSI Z223.1.
• If the factory-built fireplace has no gas access hole(s)
provided, an access hole of 1.5 in (37.5mm) or less may be
drilled through the lower sides or bottom of the firebox in a
proper workmanship like manner. This access hole must be
plugged with non-combustible insulation after the gas supply
line has been installed.
•
A shut-off valve is supplied with this unit.
• The appliance and its shut-off valves must be disconnected
from the gas supply piping system during any pressure testing
where the pressure exceeds ½ psig (3.45 KPa) or the valve
will be damaged.
Figure 35:
Gas connection location
Figure 36:
Gas valve with cover
removed
Table 7:
Orifice and Pressure Information.
E44I With Log Set
Main Burner
Natural Gas
Propane Gas
Orifice:
#31 DMS
#50 DMS
Max. Manifold Press:
3.5 W.C. (0.87 KPa)
10.0 W.C. (2.49 KPa)
Min. Manifold Press:
1.6 W.C. (0.40 KPa)
6.4 W.C. (1.60 KPa)
Max. Supply Press:
10.5 W.C. (2.62 KPa)
13.0 W.C. (3.24 KPa
Min. Supply Press:
4.0 W.C. (0.99 KPa)
8.0 W.C. (1.99 KPa)
Max. Input:
42,000 BTU/hr (12.31 KW)
36,000 BTU/hr (10.55 KW)
Min. Input:
29,000 BTU/hr (8.50 KW)
29,000 BTU/hr (8.50 KW)