Initial Installation
WARNING: Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possible death.
c
LeaRances
to
c
ombustibLes
:
Figure 24: Mantle width and height.
Maintain sufficient clearances for operation, service and maintenance.
m
inimum
f
iRepLace
s
ize
:
Table 4:
Minimum dimensions of fireplace for E44I to be installed into.
Width At Front
Width At Back
Height
Depth
Fireplace Dimensions
34” (864 mm)
24” (610 mm)
24” (610 mm)
20
3
/
8
” (518 mm)
NOTE: Space must be provided for gas line on right side of unit for servicing purposes. The E44 can only be
installed into masonary or zero-clearace fireplaces.
45”
44”
43”
42”
41”
40”
1 2
3
4
5
6
7
8
9 10 11 12
MA
NTL
E H
EIGH
T
(F
ROM UNIT BOT
TO
M)
M A N T L E D E P T H
Minimum Mantle Clearances
12” MANTLE
0” - 8” MANTLE
• A minimum distance of 23
1
/
2
” (597 mm) is
required from the centerline of the unit to the
sidewalls.
• Minimum clearance for any combustible facing is
40” (1016 mm) from the bottom of the unit.
• A 8” (203 mm) wide mantel can be mounted at
a minimum height of 40” (1016 mm) from the
bottom of unit.
• If installed with a minimum of
1
/
2
” (13 mm)
raised hearth, there must be a minimum of 16”
(406 mm) of non-combustible material in front of
the unit.
•
If installed where the hearth is flush with
the combustible flooring
, there must be a
minimum of 18” (457 mm) of non-combustible
material in front of the unit.
• Minimum ceiling clearance is 60” (1524 mm) from
bottom of unit.
n
on
-c
ombustibLe
b
uiLD
o
ut
:
The E44I / E44ID may be installed and vented into any solid fuel fireplace that has been installed in
accordance with the National, Provincial/State and local building codes and has been constructed of
noncombustible materials. Before starting, refer to please reference the information in Table 5 and Figures
26 and 27.
Additionally should extra installation depth be required, the existing fireplace may be re-faced with a build
out in front, constructed completely of non-combustible framing and finishing material (see Figure 25).
The build out must be constructed and sealed to prevent any heat from collecting in-between the existing
fireplace and the finishing material. Prior to constructing the build out it is important to know the overall
size of the selected surround panel. For ease of installation and servicing it is recommended to only have a
small overlap from the finished opening. Refer to the minimum fireplace size (Table 4) to compare with the
selected surround panel. The flex venting is permitted to have smooth sweeping, slight angle bends but
must not be kinked in any way.
IMPORTANT - Contact your local dealer for further information prior to construction and installation.