The monitoring status can be seen by users through LCD screen.
The installation is completed once the monitoring interface shows up on LCD screen.
According  to  what  shows  on  the  LCD  screen,  the  maintenance  personnel  can  see 

where the problem comes from when they are fixing the equipment.

1.If the LCD screen stays at the interface of 

unlocking

 and 

constructing

 

network

,it 

means the network construction fails. Then MI should be checked to make sure it is 
connected properly and the MI power is on.

2.If it shows on LCD screen for a long time that the the number of MI units is less than 
that of MI units connected to EnverBridge, it’s time to check whether there is a failure 
on a certain MI equipment.(As to which one is not working, please get information 
form long-distance or local server.)

3.According to the displaying interface of failure, maintenance personnel can locate 
the failure and start the maintenance work.

Safety  checks  should  be  performed  at  least  every  12  months  by  manufacturer’s 

qualified person who has adequate training, knowledge, and practical experience to 
perform these checks. The data should be recorded in an equipment log. If the device 
is not functioning properly or fails any of tests, the device has to be repaired.

To ensure safe disconnection of the EnverBridge from the solar power plant, it must 
NOT be carried out under load conditions. Ensure the following disconnection steps 
are carried out in the order shown:

1. Disconnect the AC by isolating the branch via the circuit breaker. 
    Or Disconnect the plug from the wall socket.
2. Disconnect the Ethernet cable. 
3. Remove the EnverBridge from the system.

Only trained and authorized professional personnel WHO ARE FAMILIAR WITH THE 

REQUIREMENTS OF SAFETY is allowed to perform servicing and maintenance work. 

6.5 Application

6.5 Fault display

20 minutes after data collection, a making-up network construction will take place in 

case there is any missing connection of MI. “MI connecting” which shows on the first 

line  of  LCD  1602  screen  indicates  the  connection  to  MI  is  taking  place  and “x  MI 

connected” on the second line indicates how many MI units have been connected 
with x referring to the numbers of MI units connected.

If there is a system malfunction, FAILURE shows on the displaying interface. The ID 
number(s) of failed MI can be seen on the first line of the interface with the informa

-

tion of failure following it. Please refer to 2.5 to get a detailed explanation of failure. 

What  shows  on  the  second  line  of  LCD  interface  is  the  same  as  the  monitoring 
interface of LCD.

categories

failure identification 

symbols

Explanation of failure

M

M

M

M

0

1

failure-free

the original boundary malfunction

inverter failure

ailure caused by over voltage or 

under voltage of power grid

2

3

4

5
6

0

1

2

3
4

M

M

M

M

S

S

S

S

failure caused by over frequency or 

under frequency of power grid

inner communication failure

other failures

malfunction-free

malfunction caused by over voltage 

or under voltage of power grid

malfunction caused by over 

frequency or under frequency of 

power grid

phase-locked failure

other failures

7 Disconnecting a EnverBridge from the system

8 Monitoring and Troubleshooting and Maintenance

!

WARNING

No use-serviceable parts inside, if the 
EnverBridge has any malfunctions, send it 
to authoriz ed representative or 
manufacturer. Never open and try to 
repair it by yourself

8.1 Safety checks

15

16

Summary of Contents for EnverBridge

Page 1: ...er Operating Manual Model Number EnverBridge This manual is an integral part of the unit Please read the instruction manual carefully before installation operation or maintenance Keep this instruction...

Page 2: ...id Connection 5 3 Grid Disconnect 5 4 Installation checklist 5 5 Start Up Checks 6 LCD Abstracts 6 1 Brief introduction 6 1 1 Function of LCD 6 2 LCD 1602 interface 6 2 1 Start up interface 6 3 Monito...

Page 3: ...ruction DANGER The DANGER symbols in this manual and on the EnverBridge Indicate a hazard with a high level of risk which if not avoided will result in death or serious injury CAUTION The CAUTION symb...

Page 4: ...not respond for any quality assurance and other risks For Envertech EnverBridge Warranty Terms and Conditions see the appendix of this manual 3 4 PV PCS _ Caution risk of electric shock CE mark is at...

Page 5: ...t installed environments suitable for it s IP rating CAUTION The device is intended for fixed installation Located on a part that is not removable without impairing the operation of the unit CAUTION V...

Page 6: ...07mm 3W 700g Natural convection no fans 40 65 IP65 CE 5 Years 7 8 Use the Power Line Carrier Communication PLCC technology within Photovoltaic power plant By PLCC technology EnverBridge collects gener...

Page 7: ...inverter array is exported to the utility grid Fault If the system does not operate correctly Envertech EnverBridge will stop automatically and enter into Disable mode The Envertech EnverBridge syste...

Page 8: ...these tests The data should be recorded in an equipment log If the device is not operating properly or fails any test the device has to be repaired 1 Inspect the equipment and accessories for mechanic...

Page 9: ...168 0 201 indicates a normal network connection and 192 160 0 254 indicates an abnormal network connection The figure of power efficiency which shows at the beginning of the second line indicates the...

Page 10: ...e the EnverBridge from the system Only trained and authorized professional personnel WHO ARE FAMILIAR WITH THE REQUIREMENTS OF SAFETY is allowed to perform servicing and maintenance work 6 5 Applicati...

Page 11: ...nverBridge Wear gloves and safety glasses Disconnect the EnverBridge from the Grid Isolating device Clean the EnverBridge with wet cloth carefully Introduction Use the monitoring website EnverPortal d...

Page 12: ...ill the EnverBridge serial Number in the blank space for example 90000001 click OK and finish the registration 19 20 9 Contact Zhejiang Envertech Corporation Ltd Tel 86 579 8926 6326 Email info envert...

Reviews: