27
IP2246EN
Display
Description
Selections
available
OC - Obstacle detection limit during closure [%]
Indicates the percentage of the distance travelled during
→
or after the detection of the closing limit switch
→
→
on which the reversal is deactivated.
NB: not active if
→
→
and if
→
→
.
99
TO - Setting motor 2 opening delay time [s]
Adjustment, in seconds, of the delay time for starting
the operation of motor 2, in relation to motor 1.
03
LR - Electric lock release time [s]
If enabled, this indicates the electric lock activation time at the start
of every opening operation with the automation closed.
1.5
M1 - Operation time - motor 1 [s]
Adjustment, in seconds, of the total operation time for motor 1.
i
WARNING: it is set with a sensitivity interval of 0.5 s, shown
when the decimal point on the right lights up.
Example:
= 7 seconds /
= 7.5 seconds
NB: the setting of
is only active with
→
→
.
10
M2 - Operation time - motor 2 [s]
Adjustment, in seconds, of the total operation time for motor 1.
i
WARNING: it is set with a sensitivity interval of 0.5 s, shown
when the decimal point on the right lights up.
Example:
= 7 seconds /
= 7.5 seconds
NB: the setting of
is only active with
→
→
.
10
EO - Function of output -LK+
00
- courtesy light
01
- electric lock
02
- electric lock + release stroke
03
- output active with automation closed (for electromagnets of the fail-safe type)
04
- output active with automation open
05
- output active with automation moving (can also be used for electromagnets that need
to be powered throughout the operation)
06
- output active with automation opening
07
- output active with automation closing
08
- output active with maintenance alarm triggered
09
- output active for indicating batteries almost flat
10
- ON-OFF flashing light for LED without oscillator
11
- ON-OFF flashing light
ON
- output always active
FF - Function of LP-
00
- courtesy light
01
- ON-OFF flashing light
02
- fixed light with internal oscillator
03
- output active with automation closed
04
- output active with automation open
05
- output active with automation moving
06
- output active with automation opening
07
- output active with automation closing
08
- output active with maintenance alarm triggered
09
- output active for indicating batteries almost flat
10
- ON-OFF flashing light for LED without oscillator
11
- electric lock
12
- electric lock + release stroke
ON
- output always active
BA