Pg. 41
HA8-LP Manual V. 4.0
7.3 Digital Board Specification
INPUTS
AC VOLTAGE
ACTIVATION 1
(ACT’N1)
ACTIVATION 2
(ACT’N2)
SAFETY 1
SAFETY 2
- First input to open the door. Instant Activation (i.e. push buttons)
- ON = Closed contact to ground/common.
- See Function
A”, Setting A1” for description of alternate operation
- Second input to open the door. Delayed activation.
- ON = Closed contact to ground/common.
- See Function
A”, Setting A1” for description of alternate operation.
- For Safety1 ON door will not open if presently fully closed and door will not close if presently
fully opened
- ON = Closed contact to ground/common. (i.e. overhead presence sensors [bodyguard])
- For Safety2 ON and
ACT’N1 input ON door will drive at hold speed. If ACT’N1 input OFF,
door closes. If Safety2 OFF, door will open.
- ON = Closed contact to ground/common. (i.e. Door mounted sensor on swing side [Superscan])
OUTPUTS
MOTOR
DATA
_
and DATA+
- 2 motor connectors to drive door in either clockwise or counter clockwise direction.
- Interface with BEA Bodyguard sensor. (replaces LO-21K lockout relay)
7.0 CONTROL BOARD SETTING
LINE VOLTAGE
TRANSFORMER (Hammond)
120VAC 60Hz
Low Energy
#166N24
– 24VAC – 4AMP
#166M16
– 16VAC – 3AMP
240VAC 50Hz
Low Energy
#266N24
– 24VAC – 4AMP
#266M16 - 16VAC
– 3AMP