24
3.1.3.5 Three-phase On Delay
It indicates the time required for three-phase capacitor taking and
three-phase reactor release. Enter a value between 1 and 1800 (in seconds). The factory setting is
10 seconds.
3.1.3.6 Three-phase Off Delay
It indicates the time required for three-phase capacitor off and three-
phase reactor on. Enter a value between 1 and 1800 (in seconds). The factory setting is 10 seconds.
3.1.3.7 Single phase Delay
In indicates the product’s time of reaction to load changes in a single
phase. Enter a value between 1 and 1800 (in seconds). The factory setting is 10 seconds.
3.1.3.8 Discharge Time
It is the field where the discharge time of the step is entered. If the step
type is selected as Capacitor, the discharge time will indicate the minimum time after which it will be
switched on after the step has been released. Discharge time must be set at the times determined by
the capacitor manufacturer. If a discharge coil or contactors with discharge coil is/are used, this time
might be shortened in accordance with the criteria stated by the manufacturer. Enter a value between
1 and 1800 (in seconds). The factory setting 14 seconds.