3.1.2.1 Connection Correction
It allows you to perform connection correction under the setup menu at a desired time. You must
connect 3 phase capacitor to referance step. The cpacitor to referance step. The PFC switchs on/
off the ref step for the connection correction operation. If the operation is successful it will start to the
auto setup. If it is not it gives the REF.STEP ! warning.
3.1.2.2 Current Transformer
It is the menu where primary and secondary values for the current transformer are entered. When
the product has switched to the mode to measure step powers, the values of the current transformer
must be correctly adjusted for the calculated powers to be correct. If the current transformer rates
have not been entered, they will be considered 5A / 5A when calculating capacitor powers. You
can proceed to Settings-Setup-SETUP CURR. TR. submenu to make these changes. You will be
prompted to enter CT Primary and CT Secondary values respectively. To exit the submenus after
you have made the desired changes, press HOME twice. You will be asked if you want to save the
changes or not. Use the Up and Down keys to select one of the options your product is displaying,
and press OK to save the setting.