1.2.b Front Panel Functions
POWER FACTOR CONTROLLER
RG3-15C/CS/CL/CLS
In order to enter to the menu, SET button
must be pressed for 3 seconds. In the following
sections, enter the menu means press the SET
button for 3 seconds.
3
2322 21
12
13
14
15
16
17
18
19
11
4
20
7
6
5
25
26
28
29
30
24
9
1
3
2
27
8
10
1. L1
2. L2
3. L3
4. Up Button
5. Esc Button
6. Set Button
7. Down Button
8. M LED
9. k LED
10. 1,2,3,... Step LEDs
11. SET Menu
12. OTO/MAN LED
13. Cos
j
LED
:
:
:
:
:
:
:
:
:
:
:
:
:
Display for phase 1.
Display for phase 2.
Display for phase 3.
In the menu and measuring mode, is is used to
move upwards. In the setup mode, it is used to
increase the adjusted value.
In the menu, it is used to return to the previous
process or exit from a menu. In the measuring
mode, it is used to leave the harmonic
observation mode.
It is used to enter to the menu, to access a sub-
menu and save the committed changes. In the
measurement mode, it is used to monitor the
harmonic values of voltage, current and power
parameters.
In the menu and measuring mode, is is used to
move downwards. In the setup mode, it is used
to decrease the adjusted value.
It indicates that the measured value is in mega
units and the observed value is multiplied with
106.
It indicates that the measured value is in kilo
units and the observed value is multiplied with
103.
These LEDs indicate the state of corresponding
capacitor steps of the device. If a capacitor
step is activated, the corresponding step LED
is lit. Reactor step LEDs start to light up after
the 12th step LED on RG3-15CL/CLS models.
Programmable menus which are set by pressing
SET button for 3 seconds.
This LED indicates if the operating mode is
automatic or manual. If it is continuously on, the
device is operating in Automatic Mode. If it
blinks, the device is operating in Manual Mode.
The color of this LED is green.
If Cos
j
LED is on in the menu, target Cos
j
value can be set between Inductive 0,8 and
Capacitive 0,8. If Cos
j
LED is on in the
measuring mode, Cos
j
values of related
phases are displayed.
14. PROGRAM / I LED
15. TIME / W LED
16. Capacitors/VAr LED
17. NETWORK/VA LED
18. RESET / HAR LED
19. ALARM / h LED
20. RS-485
21. C- LED
22. NORMAL LED
23. C+ LED
24.
25.
26.
27.
28.
29.
30.
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
If
PROGRAM
/I LED is on in the menu; the
switching sequence can be set in the menu. If
PROGRAM/
I
LED is on in the measuring mode,
the phase currents appear on their
corresponding phase displays.
If
TIME
/W LED is on in the menu; discharge
time, switch on delay time and switch off delay
time can be adjusted in the menu. If TIME/
W
LED is on in the measuring mode, active power
and total active power (Imp./Exp.) values of the
phases are displayed on the corresponding
displays.
If
CAPACITORS
/VAr LED is on in the menu,
the power values and connection types(R, S,
T, RST) of the steps can be set. If
CAPACITORS/
VAr
LED is on in the measuring
mode, reactive power and total reactive power
(Ind./Cap.) values of the phases are displayed
on the corresponding displays.
If
NETWORK
/VA LED is on in the menu;
current transformer ratio (Ctr), voltage
transformer ratio (Vtr) and calculation method
(Calc) can be set. If NETWORK/
VA
LED is on
in the measuring mode, apparent power and
and total apparent power values of the phases
are displayed on the corresponding phase
displays.
Press SET button for 3 seconds and enter the
menu. Select the
RESET
/HAR LED to erase
the energy values, reset the reactive energy
ratios and alarms.
Press SET button for 3 seconds and enter the
menu. Select
ALARM
/h LED to set the
boundary values for alarms(overvoltage,
reactive/active ratio and harmonics).
In this menu; settings related to the RS-485
communication protocol(baudrate, address,
parity) are set.
This LED indicates that RG3-15C/CS/CL/CLS is
waiting to switch off capacitor steps.
This LED indicates that RG3-15C/CS/CL/CLS
will not switch any capacitor steps on or off.
This LED indicates that RG3-15C/CS/CL/CLS is
waiting to switch on capacitor steps.
Incase of a failure, alarm relay switches on and
alarm LED lights up.
In case of a connection failure, this LED lights
up.
If reactive energy ratios go beyond user-defined
values, this LED lights up.
If voltage harmonic ratios go beyond user-
defined values, this LED lights up.
When target Cos
j
value is not reached even
though all of the capacitor steps are switched
on(insufficient step power for target
compensation), this LED lights up.
If there isnt a capacitor connected to a step,
capacitor step failure LED lights up.
If the voltage value exceeds the user-defined
overvoltage, this LEDC lights up.
AUTO