RG3-15CS/CLS models have MODBUS-RTU communication protocol. All

measured parameters can be saved into computer’s memory via appropriate

software.Additionally, all necessary configurations also can be set via a

computer with the software installed on it.

NOTE: Computer communication feature is only available for

RG3-15CS/CLS models.

3.10 PC Communication Settings (RS-485)

POWER FACTOR CONTROLLER

RG3-15C/CS/CL/CLS

21

By changing the device address setting, communication up to

247 devices can be achieved.

3.10.a Device Address Setting (485 Adr)

Press the “SET” button for 3 s in order to enter the menu.

Using the 

“UP/DOWN”

 buttons, find computer communication

menu (RS-485).

Using the 

“UP/DOWN”

 buttons, select 

“yES”

 to reset the energy

counters or select 

“no”

 to cancel the resetting and press the

“SET”

 button.

SAUE

If you want to leave the setup menu without making any other

changes, press the 

“ESC”

 button until 

“SAVE SEt yES”

 shows

on the screen. If you want to save the changes, press the 

“SET”

button. If not, press the 

“ESC”

 button.

3.9.c Conditioning the Energy Counters to Work

with the Generator Input

The conditioning of the energy counters is done in this menu.

There are 2 parameters. If the “gEn ACt no” parameter is selected,

Energy Counter 1 and Energy Counter 2 will count simultaneously.

If the “gEn ACt yES” parameter is selected; when a signal on the

generator input exists, Energy Counter 1 stops counting and

Energy Counter 2 starts to count. When the signal disappears,

Energy Counter 2 stops counting and Energy Counter 1 starts to

count. This way, Energy Counter 2 can be set as a generator

energy counter.

To enter to the Energy menu, press the 

“SET”

 button. The first

option in the Energy menu is the Active Import Energy Value

(A-I).

Using the 

“UP/DOWN”

 buttons, find the menu for conditioning

the energy counters(Engy SET gEn).

Press the 

“SET”

 button to enter this menu. “gEn ACt no” will be

displayed.

In order for the energy counter 1 to stop counting and energy counter to

start counting when there is a signal on the generator input, select 

“yES”

or in order for the energy counters to count simultenaously, select 

“no”

using the 

“UP/DOWN”

 buttons and press the 

“SET”

 button.

SAUE

If you want to leave the setup menu without making any other

changes, press the 

“ESC”

 button until 

“SAVE SEt yES”

 shows

on the screen. If you want to save the changes, press the 

“SET”

button. If not, press the 

“ESC”

 button.

Summary of Contents for RG3-15C

Page 1: ...ischarge Time Settings 8 3 5 Power Value and Connection Type Settings for Capacitors 10 3 6 Current and Voltage Transformer Ratio Settings 12 3 7 Reset Settings 14 3 8 Alarm Settings 15 3 9 Resetting...

Page 2: ...3 12C CS s housing There are no user servicable parts inside it RG3 12C CS is connected to the network by means of a current transformer Do not disconnect the current transformer terminals If you disc...

Page 3: ...o the device at the same time RG3 15C CS CL CLS ile Yap labilecek l mler Phase Voltage L1 2 3 N Measurement Phase Current L1 2 3 N Measurement Cosj Value L1 2 3 N Measurement Average Ind Cap Cosj Valu...

Page 4: ...23 C LED 24 25 26 27 28 29 30 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on their correspon...

Page 5: ...L l2 k2 K L l3 k3 Alarm Relay Generator Input 110 250 V AC C12 C11 C10 C9 C8 C7 C5 C4 C3 C2 C1 C13 C14 C15 C6 RG3 15C CS Current value of 3 Phase fuses which are connected to protect the capacitors mu...

Page 6: ...tched to the generator operation for any generator starts including the ones for maintaining purposes a b c After the device is energised it finds connection errors and corrects them automatically Pow...

Page 7: ...the option on is selected in the automatic setup menu the automatic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be che...

Page 8: ...nection option To change this setting press the SET button When Auto connection is on the device controls its connection automatically at start up and corrects any existing measurement input errors If...

Page 9: ...WN buttons select the Program Prog menu When program menu is displayed program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SE...

Page 10: ...not press the ESC button Enter a value between 1 1800 seconds and then press SET button Using the UP DOWN buttons enter to another menu option which you wish to change If you are not going to change...

Page 11: ...PS 10 is selected power value of the first capacitor step is measured and other steps power values are calculated according to selected program Note When setup parameter is selected as on in Auto menu...

Page 12: ...until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value sett...

Page 13: ...Transformer Ratio Setting To obtain accurate power values when calculating the capacitor step powers current and voltage transformer ratios must be entered correctly If these ratios are entered incor...

Page 14: ...the screen If you want to save the changes press the SET button If not press the ESC button In this menu voltage transformer ratio can be set between 1 2000 For Example For a 34 5 kV 100 V transformer...

Page 15: ...selected Reset LED turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Select yES...

Page 16: ...arm Setting 3 8 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 8 a a Overvoltage Setting SAUE If you want to leave...

Page 17: ...the overvoltage delay time setting menu SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the ch...

Page 18: ...e ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Page 19: ...erthemenu Using the UP DOWN buttons find the alarm menu ALr When alarm menu is selected alarm LED turns on Press the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over volt...

Page 20: ...uttons SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not...

Page 21: ...the energy values can be entered with 0 1 kWh kVArh precision for both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the gener...

Page 22: ...ut The conditioning of the energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gE...

Page 23: ...ud rate menu bAUd SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET bu...

Page 24: ...n be changed and activated in this menu When the password is activated a pin code is always required before entering the menu Thus user password prevents any change to the settings of the device by un...

Page 25: ...new password press the SET button Enter the new password again and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to...

Page 26: ...nics When Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displ...

Page 27: ...is phase is export active power Currents I and HAR LEDs on the display indicate that displayed values indicate current harmonic values By pressing the SET button repeatedly THD and odd numbered harmon...

Page 28: ...are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on the...

Page 29: ...import energy and the remaining numbers show the energy value such as 203385706 8 kWh While active import energy is displayed if the DOWN button is pressed active export energy is displayed In the ex...

Page 30: ...ion Error Compensation Error Defected 1st capacitor step or loads are too variable Target Cosj is capacitive even when all capacitor steps are switched off Capacitor powers are not sufficient for targ...

Page 31: ...long int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10...

Page 32: ...6 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE VECTO...

Page 33: ...00A5 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160...

Page 34: ...800B 800C 800D 800E 8012 8013 8014 8015 8016 8017 8018 8019 801A 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 8094 8095 8096 8097 8098...

Page 35: ...ION 1ST CAPACITOR STEP SWITCH ON OFF 2ND CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OF...

Page 36: ...R RG3 15C CS CL CLS 35 In the first column total reactive power values of 3 phase capacitors and in second third columns reactive power values of the capacitors in single phase system are shown CAPACI...

Page 37: ...0 V AC 3 0 s Off 7 0 1 0 s Off 25 15 96 hours 1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Conta...

Reviews: