Troubleshooting an Enphase System
2014 Enphase Energy Inc.
August 2014
38
To send the
clear-dc-resistance-low
message to a microinverter:
1.
From the Envoy Administration menu, choose
Device Conditions and Controls
.
NOTE
: Do not check the box in the
Select
column.
2.
Click the
serial number
of the unit displaying DC
Resistance Low - Power Off
.
The Control Flags screen displays.
CAUTION
: Do not select the
reboot
and
cmd-alert
control flags unless recommended by
Enphase. The functions are:
reboot
- reboots the inverter
cmd-alert
- clears a condition flag for a command sent
3.
In the
clear-dc-resistance-low
menu, click the
set
box.