INTRODUCTION

 

 
The W‐TRAC is a supervisory controller for Engineered Air HRW heat wheels, with built in discharge air 
temperature control and optional exhaust frost control. 
 
The information used in this manual should be used in conjunction with the unit function sheet(s) and the 
HRW series Installation, Operation, and Maintenance manual. 
 
The W‐TRAC is designed to control only Engineered Air equipment.  Various upgrades and improvements 
have been made over time.  Always include any suffix letters and numbers for troubleshooting and/or 
replacement.  All W‐TRAC models are backwards compatible; however some additional wiring may be 
required.   
 
Note: It is necessary that all of the remote wiring and controls be complete and operational before starting 
the appliance. 
 
 

CONTROLLER

 

RATINGS

 

 
Power requirements: 24 VAC, 40 VA. 
Contact Rating: 120V 3A inductive 
0‐10 Vdc input impedance: 5 k

 

Environment: ‐40 to 120°F (‐40 to 50°C) non‐condensing. 
 

Summary of Contents for EngA W-TRAC

Page 1: ...ORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 4774 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 583 1406 1175 TWINNEY DRIVE NE...

Page 2: ...a safe place The other set is attached to the control panel door and should never be removed Please report any omissions to the national service manager Warning Improper installation adjustment altera...

Page 3: ...A W TRAC IOM 49 3 of 12 Mar 99 R4...

Page 4: ...7 TEMPERATURE CONTROL 7 BASE SETPOINT 8 SETPOINT RESET 8 FROST CONTROL 8 EXHAUST AIR RH SENSOR 8 RETURN AIR RH SENSOR 9 BDRH PREDICTED RETURN AIR RELATIVE HUMIDITY 9 WIRING 9 SENSOR TABLE 12 SERVICE N...

Page 5: ...AC is designed to control only Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement...

Page 6: ...d style DC drive motors P2 Wiper output potentiometer legacy for old style DC drive motors P3 High output potentiometer legacy for old style DC drive motors DIP SWITCHES W TRAC configuration options a...

Page 7: ...y experienced and qualified personnel POT Description DIS CAL Discharge temperature sensor calibration EX CAL Exhaust temperature sensor calibration AMB CAL Ambient outdoor temperature sensor calibrat...

Page 8: ...put voltage to terminals S and C1 with a setpoint fixed at 66 F Refer to the equipment function page for the design reset range Input Voltage 0 0 2 0 4 0 6 0 8 0 10 0 Discharge Setpoint F C No Resisto...

Page 9: ...values are expected to be reasonably constant In these cases the W TRAC operates by sensible temperature only When enabled the BDRH pot Building Design Relative Humidity is set according to the expec...

Page 10: ...ers Refer to the equipment wiring diagram for connection details The following setup parameters are typical Always refer to the equipment function sheet for any changes To ensure proper setup operatio...

Page 11: ...the temperature at the sensing element Compare these readings to the sensor table values If the resistance is out by more than 16 ohms replace the sensor Measuring a sensor temperature between 60 70...

Page 12: ...RH SENSOR TABLE Sensor Resistance Chart for TE6000EA3 Table 2 C F Resistance C F Resistance C F Resistance 40 40 602 18 3 65 983 48 9 120 1234 34 4 30 633 20 68 996 54 4 130 1269 28 9 20 665 20 6 69 1...