background image

A

 

 

W-TRAC

 

 
 

IOM‐49 

                           10 of 12 

Mar 99  R4 

 

 
 

(over 50 ft. eq. length), the use of a minimum 20 gauge‐shielded wire is recommended. The shield should 
be grounded at the controller end only, with the other end taped. 
 
It is important to ensure correct polarity when wiring into the system.  
 

NOTE: Field analog control inputs require signal isolation to prevent ground loop 
signal corruption and/or damage to the controller(s). 

 
 

SERVICE

 

NOTES

 

 

ROTATION

 

 
Most heat wheels have a purge section to purge exhaust air trapped in the wheel flutes before they rotate 
to the supply air side.  The correct wheel rotation direction is noted on the face of the heat wheel.  Drive 
motor rotation may be changed at the motor wire connections or on the inverter drive feeding the motor 
(if used). 
 

MOTOR

 

SPEED

 

CONTROL

 

 
The modulating 0‐10Vdc motor speed output may be connected to a variety of controllers and/or 
inverters.  Refer to the equipment wiring diagram for connection details.  The following setup parameters 
are typical.  Always refer to the equipment function sheet for any changes.  To ensure proper setup 
operation, do not have DIP 4 and DIP 5 on at the same time. 

 

KBVF / SIVF(R) 

The KBVF inverter drive and SIVF signal isolator are manufactured by KB Electronics Inc.  The inverter and 
isolator installation and operation manuals are included in the information package, originally located in 
the main equipment electrical panel.  The 0‐10Vdc W‐TRAC control output feeds into the SIVF signal 
isolator which, in turn, feeds an isolated 0‐5Vdc signal to the KBVF inverter drive.   
 
High Speed 
 
Turn on W‐TRAC DIP 4 to force the W‐TRAC to maximum output (near 10Vdc).  Note that if the  
W‐TRAC is operating in frost mode DIP 4 will not allow the drive to go to full speed.  Measure the motor 
amps and confirm the readings are less than the maximum motor ampacity.  If possible, measure and 
confirm the output frequency is 60Hz. 
 
The KBVF is factory set to 100% of rated frequency (60Hz) and should not be adjusted. 
 

Summary of Contents for EngA W-TRAC

Page 1: ...ORY CANADIAN EASTERN FACTORY 1401 HASTINGS CRES SE CALGARY ALBERTA T2G 4C8 Ph 403 287 4774 Fx 888 364 2727 32050 W 83rd STREET DESOTO KANSAS 66018 Ph 913 583 3181 Fx 913 583 1406 1175 TWINNEY DRIVE NE...

Page 2: ...a safe place The other set is attached to the control panel door and should never be removed Please report any omissions to the national service manager Warning Improper installation adjustment altera...

Page 3: ...A W TRAC IOM 49 3 of 12 Mar 99 R4...

Page 4: ...7 TEMPERATURE CONTROL 7 BASE SETPOINT 8 SETPOINT RESET 8 FROST CONTROL 8 EXHAUST AIR RH SENSOR 8 RETURN AIR RH SENSOR 9 BDRH PREDICTED RETURN AIR RELATIVE HUMIDITY 9 WIRING 9 SENSOR TABLE 12 SERVICE N...

Page 5: ...AC is designed to control only Engineered Air equipment Various upgrades and improvements have been made over time Always include any suffix letters and numbers for troubleshooting and or replacement...

Page 6: ...d style DC drive motors P2 Wiper output potentiometer legacy for old style DC drive motors P3 High output potentiometer legacy for old style DC drive motors DIP SWITCHES W TRAC configuration options a...

Page 7: ...y experienced and qualified personnel POT Description DIS CAL Discharge temperature sensor calibration EX CAL Exhaust temperature sensor calibration AMB CAL Ambient outdoor temperature sensor calibrat...

Page 8: ...put voltage to terminals S and C1 with a setpoint fixed at 66 F Refer to the equipment function page for the design reset range Input Voltage 0 0 2 0 4 0 6 0 8 0 10 0 Discharge Setpoint F C No Resisto...

Page 9: ...values are expected to be reasonably constant In these cases the W TRAC operates by sensible temperature only When enabled the BDRH pot Building Design Relative Humidity is set according to the expec...

Page 10: ...ers Refer to the equipment wiring diagram for connection details The following setup parameters are typical Always refer to the equipment function sheet for any changes To ensure proper setup operatio...

Page 11: ...the temperature at the sensing element Compare these readings to the sensor table values If the resistance is out by more than 16 ohms replace the sensor Measuring a sensor temperature between 60 70...

Page 12: ...RH SENSOR TABLE Sensor Resistance Chart for TE6000EA3 Table 2 C F Resistance C F Resistance C F Resistance 40 40 602 18 3 65 983 48 9 120 1234 34 4 30 633 20 68 996 54 4 130 1269 28 9 20 665 20 6 69 1...

Reviews: