Keypad Parameters Related to PROFInet Communication Module
5.1
CNF Group
5.1.1
[CNF-30] Option-1 Type: the type of device installed in the module slot 1
Automatically detects and displays the type of communication module installed. “PROFInet” is
displayed when a PROFInet communication module is installed in the Sinus H inverter.
5.2
DRV Group
5.2.1
[DRV-06] Cmd Source: Command Source Selection
Selects the command source for the Sinus H inverter. Set the parameter to [4 FieldBus] to set
PROFInet communication as the command source.
5.2.2
[DRV-07] Freq Ref Src: Frequency Reference Source Selection
Selects the frequency reference source for the Sinus H inverter. Set the parameter to [8 FieldBus] to
set PROFInet communication as the frequency reference source.