PROFInet Module
SINUS H
23
/
34
7.2.2
Status Word (ZSW1)
Bit
Name
Value
Description
0
RDY_ON
1
Ready for Switch ON
(Operation is available.)
0
Not Ready for Switch OFF
(Operation is not available.)
1
RDY_OPERATION
1
Bit 0 value of the control word (STW1) that has
been input.
0
2
OPERATION
1
Bit 3 value of the control word (STW1) that has
been input.
0
3
Fault Present
1
Fault condition is present at the inverter.
No Fault
0
Fault condition is not present at the inverter.
4
No OFF2
1
Bit 1 value of the control word (STW1) that has
been input.
OFF2
0
5
No OFF3
1
Bit 2 value of the control word (STW1) that has
been input.
OFF3
0
6
SWC_ON_INHIB
1
Switching On inhibited
(Control is not available.)
0
Switching On Not inhibited
(Control is available.)
7
Warning Present
1
Warning condition is present at the inverter.
No Warning Present
0
Warning condition is not present at the inverter.
8
Speed Error within tolerance
1
The motor speed has reached the frequency
reference (“Setpoint value”).
Speed Error out of tolerance
0
The motor speed has not reached the frequency
reference (“Setpoint value”).
9
Control Requested
1
Bit 10 value of the control word (STW1) that has
been input.
No Control Requested
0
10
ABOVE_LIMIT
-
Not supported
11 to 15
-
-
Reserved
“bits 0 to 2” and “bit 6” indicate the following communication module status, as explained in <10.
PROFIdrive Status Diagram>.
Status Word
Status
xxxx xxxx x1xx x000
“Switching On Inhibited”
xxxx xxxx x0xx x001
“Ready For Switching On”
xxxx xxxx x0xx x011
“Ready For Operation”
xxxx xxxx x0xx x111
“Operation”