background image

ACTIVATION 

Before gas is admitted to the burner, at least two faultless ‘dry runs’ must have taken place.  No interlock may 
be by-passed during these runs. 

 

Dry Run 
1.  By means of pressure test nipples and with both manual isolating valves closed, using air or inert gas, test 

the burner valvetrains for leaks, and the safety shut-off valves for pressure tightness. 

 
2.  Start the main duct fan. 

 
3.  Adjust the pressure switch to 1.9 mbar (0.7in wg). 

 
4.  Make electricity available to the system. 

 
5.  Check by manipulation of the control instrument that the modulating motor and butterfly valve operate 

correctly.  Remove the link between motor and valve, and close the valve by hand. 

 
6.  Operate the ‘Burner Run’ button.  The combustion air fan (if fitted) should start, and following the purge 

period a spark should appear at the burner.  About 10 seconds after the spark is initiated the spark should 
stop, and because no gas is available the control should go to ‘lockout’. 

 

If the spark fails to appear:- 
a.  Check the spark gap.  It should be 2-3 mm. 
b.  Check the electrical circuit. 
c.  Check the settings of the pressure switches. 
d.  Check all interlocks. 
 
Repeat the test. 

 
Live Run 

7.  Make certain the ball valve between the motorised butterfly valve and the burner is closed. 
 

Adjust the valve train governor to give the minimum possible gas pressure. 

 

Open the ball valve at the inlet to the valve train. 

 
8.  Operate the ‘Burner Start’ button, the pilot should light.  If it does not light after three attempts: 

a.  Check that the pilot gas valve is operating. 

 
b.  Adjust the adjustable port pilot cock as follows, starting with the cock two turns open: 
 

Remove the top hexagon screw cap c/w washer.  The slotted head adjusting screw now exposed is 
turned clockwise for less gas and counter-clockwise for more gas. 

 
 

For flame rod system the proper amount of pilot gas is the minimum that will reliably ignite each time 
the spark electrode is energised.  A scanner system will require a slightly larger pilot than a flame rod 
system. 

 
Repeat the test. 
 
9.  Run the motor to its lowest position and try to start the burner.  if a stable low flame is not obtained, or if the 

flame is too large, it may be necessary to adjust the butterfly valve slightly against the clutch.  When this 
has been done, screw in the ‘bottom’ adjusting screw until it just touches the stop, and tighten the locknut. 

 
10.  If any adjustment has subsequently to be made to the high fire rate, it must be done by adjusting the gas 

pressure and not by adjusting the butterfly valve.  If the high fire rate is altered it may be necessary to 
adjust the low fire rate by following the above procedure  from 1. above.  If this method is not followed the 
control characteristics of the valve and motor will be spoilt. 

 
 

MAINTENANCE 

To ensure the continuing fault-free operation of the burner, the following operations should be undertaken every 
six months: 

1. 

Clean the working faces of the burner with a stiff brush. 

2. 

Clean the fan impeller (a dirty impeller will cause a dirty flame). 

3. 

Check all safety circuits. 

4. 

Check pressure, etc, against the values recorded when the burner was commissioned. 

 

 
 

Page 2 

 

Summary of Contents for Nu-way MULTIPLEX ENERGYSTREAM ES Series

Page 1: ...tral wires are connected to their appropriate terminals as reversal could present a hazard also the earth bonding must be checked to ensure a good connection poor earth connections are often the cause of faulty burner operation when using flame probe detection GAS PIPING MUST NOT BE USED FOR EARTHING All electrical interlocks should have been installed and tested for correct operation before commi...

Page 2: ...fter three attempts a Check that the pilot gas valve is operating b Adjust the adjustable port pilot cock as follows starting with the cock two turns open Remove the top hexagon screw cap c w washer The slotted head adjusting screw now exposed is turned clockwise for less gas and counter clockwise for more gas For flame rod system the proper amount of pilot gas is the minimum that will reliably ig...

Page 3: ...t fan rotation c Fan blades dirty a Reset switch b Correct c Clean fan 3 No spark Burner goes to lockout a High tension lead not properly tightened at terminations b Spark plug nor properly adjusted c Transformer failed a Tighten lead ends b Adjust as necessary c Change transformer 4 Pilot does not light a No gas b Too much gas c Pilot valve not opened a Find cause and rectify b Adjust gas pilot c...

Page 4: ...ckout a High or low gas pressure switch if fitted faulty b Duct pressure switch faulty c Loss of duct air pressure d Interlock operated a Rectify switch b Rectify switch c Check main duct fan d e make interlock 10 Flame goes out Burner goes to lockout a Loss of gas b Loss of combustion air c Failure of flame detector a Turn off gas and investigate b Check combustion air fan c Change detector 11 Bu...

Page 5: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk ...

Reviews: