171 425 77 16-01
2(2)
ELECTRIC EQUIPMENT
Oil burner control: LMO24.255
List of components
A1
Oil burner control
B1 Photoresistor
F1
Operating fuse
F2 Fuse
F3 Fuse
H1
Lamp, low capacity
H2
Lamp, high capacity
K1
Thermal overload protection
M1
Burner motor
S1
Operating switch
S2 Operating switch, high/low capacity
S3
Control thermostat
S4
Temperature limiter
S5
Micro switch for hinged door
Function
1. Switch on operating switch and twin thermostat
The burner motor starts, an ignition spark is formed, the prepurge goes
on till the prepurge period expires and the solenoid valve 1 opens (2).
2. Solenoid valve 1 opens
Oil mist is formed and ignited. The photocell indicates a lame.
3. The safety time expires
a. If no lame is established before this time limit the control cuts out.
b. If for some reasons the lame disappears after this time limit,
the burner will make an attempt to re-start.
4. Full load thermostat ON
The burner is in operating position and can now change between high
and low capacity.
4-5. Operating position
If the burner operation is interrupted by means of the main switch or the
thermostat, a new start takes place when the conditions in accordance
with point 1 are fulilled.
The oil burner control cuts out
A red lamp in the control is lit. Press the reset button and the burner
re-starts.
S6 Control thermostat, high/low capacity
S7
Main switch
S20 Main switch
T1
Ignition transformer
X1
Connection terminal board
X2
Earth terminal
X3
Plug-in contact "Euro", burner
X4
Plug-in contact "Euro", boiler
X5 Plug-in contact "Euro", high/low burner
X6 Plug-in contact "Euro", high/low boiler
X7
Plug-in contact "Euro" 3-phase, burner
X8
Plug-in contact "Euro", 3-phase, boiler
Y0
Solenoid valve start
Y1
Solenoid valve 1
Y2
Solenoid valve 2
Technical data
Pre-ignition time:
25 s
Pre-purge time:
25 s
Post-ignition time:
5 s
Safety lock-out time:
5 s
Reaction time on lame failure:
max. 1 s
Ambient temperature:
from - 20 to +60°C
Min. current with lame established:
30 µ A
Max. photo current at start:
5,5 µ A
Enclosure:
IP 40
Control of photo current
Current through photo unit is measured with a d.c. ammeter (a moving coil
instrument connected in series with the photo unit).
Mains connection and fuse in accordance with local regulations.
Max loading K1
Connection A1,A2 / 95, 96 / 97, 98 Max 0,2A/15W